5
Electrical installation
Installation instructions
Operating Instructions – MOVI-C
®
FIELD CONTROLLER standard/advanced
38
5.3
Installation instructions
5.3.1
Permitted voltage systems
Information on voltage systems
Information on permissibility
TN and TT systems – voltage systems
with directly grounded star point
Can be used without restrictions
IT systems – voltage systems with non-
grounded star point
Contact SEW‑EURODRIVE
Voltage systems with grounded outer
conductor
Not permitted
5.3.2
Connecting supply system cables
• The nominal voltage and frequency of the device must correspond with the data of
the supply system.
• Dimension the cable cross section according to the input current I
line
for nominal
power (see chapter "Technical data and dimension sheets").
• Install safety equipment F11/F12/F13 for line fuses at the beginning of the power
supply cable behind the supply bus junction, see chapter "Connection diagram".
Dimension the safety features according to the cable cross section.
• Use only copper conductors with a minimum temperature range of
90
°C as con-
nection cable.
26872137/EN – 12/2021