10
Technical data and dimension sheets
Port overview
Operating Instructions – MOVI-C
®
FIELD CONTROLLER standard/advanced
143
10.4
Port overview
10.4.1
Interface description
The interfaces of the
MOVI‑C
®
FIELD CONTROLLER
have the following functions:
• X43_1/X43_2 – EtherCAT
®
/SBus
PLUS
interface for the master port
• X4233_1/X4233_3 – fieldbus interfaces for the slave port
• X4224 – engineering interface
• X9 – system bus interface and RS485 interface
10.4.2
Engineering interface
INFORMATION
Ports 21 and 23 are initially closed and can be opened via the configuration.
Port
TCP/
UDP
Function
Authorization
21
TCP FTP
Reading from and writing to the file system
23
TCP Telnet
Reading OEM diagnostic data
310
TCP/
UDP
Data Streaming
Reading and writing of all indexed parameters
11740 –
11743
TCP CODESYS engineering
Read and write
1740 - 1743 UDP CODESYS engineering
Read and write
4840
CODESYS OPC UA server
8080
HTTP CODESYS web server
10.4.3
PROFINET
Port
TCP/
UDP
Function
Authorization
Dynamic
port defini-
tion via End
Point Map-
per
UDP PROFINET DCE/RPC
Reading and writing on all indexed parameters
Ethertype 8892hex Process data exchange
Controlling connection
Ethertype 88B5hex Address Editor from
SEW‑EURODRIVE
Reading and writing of all address parameters
of the Ethernet interface
310
TCP/
UDP
Data Streaming
Reading and writing of all indexed parameters
161
UDP SNMP
Reading on MIBs
80
TCP Integrated web server
Read
26872137/EN – 12/2021