Operation

Operating notes

Addendum to the Operating Instructions – GBG10..A..

14

5

Operation

5.1

Operating notes

 WARNING

Risk of crushing due to possible restart after re-establishment of the power supply or
presence of the signals at the STO inputs.

Severe or fatal injuries.

In  emergency  situations,  set  the  "MODE"  switch  to  "AUTO"  position  and  the
rotary switch to "STOP".

 WARNING

Risk of crushing due to unexpected startup of the drive unit.

Severe or fatal injuries.

Before  deactivating  local  mode,  take  measures  to  prevent  the  drive  unit  from
starting up unintentionally, e.g. by activating "STO".

Observe the requirements for local mode in chapter "Startup".

5.2

Control elements

The following figure shows the control elements of the CBG10..A keypad:

MODE

AUTO

MODE

LOCAL

SPEED

f1

SPEED

f2

BRAKE

AUTO

BRAKE

MANUAL

MO

VI

G

EAR

(R

)/

D

R

C

 C

O

N

T

R

O

L

L

BO

X

(SN

I/

D

SC

/D

AC

)

RESET

STOP/RESET

C

W

C

C

W

[1]

[2]

[3]

[4]

[5]

20744968971

[1] "MODE" switch

Changeover between automatic mode and local mode

[2] "SPEED" switch

For selecting speed setpoint f1/f2

[3] "BRAKE" switch

For deactivating brake release or DynaStop

®

 without drive

enable

[4] "RESET" button

Fault reset

[5] Rotary switch

For CCW enable/stop/CW enable

23569654/EN – 07/2017

Содержание GBG10 A Series

Страница 1: ...23569654_0717 Drive Technology Drive Automation System Integration Services Addendum to the Operating Instructions Keypad GBG10 A Edition 07 2017 23569654 EN...

Страница 2: ...SEW EURODRIVE Driving the world...

Страница 3: ...licable documentation 6 2 Device structure 7 2 1 GBG10 A keypad 7 2 2 Type designation 9 3 Electrical installation 10 3 1 Connecting the GBG10 A keypad 10 4 Startup 11 4 1 Startup notes 11 4 2 Activat...

Страница 4: ...ng table shows the grading and meaning of the signal words for safety notes Signal word Meaning Consequences if disregarded DANGER Imminent hazard Severe or fatal injuries WARNING Possible dangerous s...

Страница 5: ...ushing Warning of suspended load Warning of automatic restart 1 2 3 Structure of embedded safety notes Embedded safety notes are directly integrated into the instructions just before the de scription...

Страница 6: ...age to equipment or property resulting from non observance of these operating instructions In such cases SEW EURODRIVE assumes no liability for defects 1 5 Product names and trademarks The brands and...

Страница 7: ...example of keypad GBG10 11A 00 MODE AUTO MODE LOCAL SPEED f1 SPEED f2 BRAKE AUTO BRAKE MANUAL MOVIGEAR R DRC CONTROLLBOX SNI DSC DAC RESET STOP RESET CW CCW 2 3 1 20736929419 1 M23 plug connector 2 C...

Страница 8: ...ts For connecting the keypad to the drive unit the drive unit must be equipped with the following plug connector X5131 SNI or DSC designs X5132 DAC designs To operate the drive unit in local mode with...

Страница 9: ...AR DRC 13575848 2015 1000001 Supply voltage Rated current Maximum current Protection type Temperature 24 V DC 40 mA 60 mA IP20 25 60 C 20738431115 2 2 2 Type designation The following table shows the...

Страница 10: ...t connection of keypad and drive unit The GBG10 A keypad is not designed for permanent connection within a system Damage to the device Disconnect the keypad from the drive unit after use and remove it...

Страница 11: ...of crushing due to possible restart after re establishment of the power supply or presence of the signals at the STO inputs Severe or fatal injuries In emergency situations switch the MODE switch to A...

Страница 12: ...ode is not possible with this setting When DIP switch S2 3 is set to ON you can control the drive unit in automatic mode bus control or local mode depending on the position of the MODE switch 4 2 1 Re...

Страница 13: ...nhibited From version 16 From version 14 OFF S2 ON 1 2 3 4 Inhibited ON S2 ON 1 2 3 4 Enabled or inhibited 1 Required drive status for switching to local mode 4 4 Setting the speed setpoints Set the s...

Страница 14: ...mode take measures to prevent the drive unit from starting up unintentionally e g by activating STO Observe the requirements for local mode in chapter Startup 5 2 Control elements The following figure...

Страница 15: ...rive unit LOCAL STOP X AUTO 0 Local mode Stop no enable by drive unit LOCAL CCW f1 AUTO 0 Local mode CCW rotation with f1 by drive unit LOCAL CCW f2 AUTO 0 Local mode CCW rotation with f2 by drive uni...

Страница 16: ...tor P insert SpeedTec cap able company Intercontec male 0 coded Cable length 1 m Interference immunity Meets EN 61800 3 2 Environment Interference emission Meets category C1 according to EN 61800 3 Am...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...SEW EURODRIVE Driving the world SEW EURODRIVE GmbH Co KG P O Box 3023 76642 BRUCHSAL GERMANY Phone 49 7251 75 0 Fax 49 7251 75 1970 sew sew eurodrive com www sew eurodrive com...

Отзывы: