Operating Instructions – Explosion-Proof AC Motors DR63/eDR63, DVE250/280
31
5
Motors of category 2G, 2GD, 3D and 3GD
Electrical Installation
5.14 Motors of category 2G, 2GD, 3D and 3GD
5.14.1 General information
The explosion-proof SEW-EURODRIVE motors are designed for use in the following
zones:
5.14.2 Special designation "X"
If the special indication "X" appears after the certification number on the declaration of
conformity or the prototype test certificate, the certificate contains special conditions for
safe use of the motors.
1139608587
[1] Hex nut
[2] Washer
[3] PE conductor with cable lug
[4] Serrated lock washer
[5] Stud
[6] Terminal box
[1]
[1]
[5]
[5]
[4]
[3]
[6]
[2]
[2]
[4]
[3]
[6]
Motor category
Area of operation
2G
Use in zone 1 and compliance with the design requirements for equipment group
II, category 2G.
2GD
Use in zone 1 or 21 and compliance with the design requirements for equipment
group II, category 2GD.
3D
Use in zone 22 and compliance with the design requirements for equipment
group II, category 3D.
3GD
Use in zone 2 or 22 and compliance with the design requirements for equipment
group II, category 3GD.