Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
93
10
PROFINET configuration with topology detection
PROFINET IO Configuration
10.3.4 Topology diagnostics
Topology errors are reported to the PROFINET IO controller as diagnostics alarms. In
the event of an error, the EXTF-LED of the PROFINET IO controller is lit. The error is
also indicated by a red cross [1] in STEP 7 HW Config.
Possible causes:
• ETHERNET ports mixed up
• Wrong port property settings
• Units cannot be addressed
Proceed as follows to display information on an error:
1. Select the unit or the respective slot.
2. Right-click and select 'Module status' from the context menu.
A window is displayed.
3. Select the 'Communication diagnostics' tab.
64635AXX
[1]
[1]
[1]
[1]
'Red cross' symbol for error