Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
121
12
Diagnostic procedure
Error Diagnostics on PROFINET
12.1.2 Diagnostics problem 2: No process data exchange with the I/O controller
• Check the settings in the higher-level I/O controller again.
Is the user program switched off correctly? (See sample program in chapter 'Process
data exchange with the MOVI-PLC
®
advanced
DHR41B" controller')
• Check the settings in MOVI-PLC
®
advanced
DHR41B (see chapter "Settings in
MOVI-PLC
®
advanced
DHR41B")