Manual – MOVI-PLC® advanced DHR41B for EtherNet/IP, Modbus/TCP and PROFINET IO
12
Diagnostic procedure
Error Diagnostics on PROFINET
12.1.1 Diagnostics problem 1: MOVI-PLC
®
advanced
DHR41B not working on PROFINET IO
Initial status:
•
DHR41B option is physically connected to PROFINET IO
•
DHR41B option has been configured in the IO controller and bus communication is
active
↓
Ethernet bus connector X30:1, X30:2 plugged in?
No
→
[A]
Yes
↓
Yes
↓
Response of the Link
LED?
OFF
→
[C]
Response of the
BUS FAULT LED?
Yellow
→
Red
→
[B]
[C]
Green
↓
Off
↓
DHR41B option has no connection to Ethernet.
↓
Check the configured and set PROFINET name.
↓
PROFINET names identical?
No
→
[D]
Yes
↓
You may have configured an incorrect unit type or defined the configuration incorrectly.
↓
Delete configuration for the DHR41B option from the PROFINET IO network.
↓
Configure the DHR41B option again, selecting the unit designation "SEW-DHR41B".
Assign the address range for your control system.
↓
Now load the configuration in the PROFINET IO controller and start the bus communi-
cation again.
[A]
Check the bus cabling.
[B]
The DHR41B option was not yet configured or configured incorrectly.
Check the configuration, particularly the device name and the IP
address.
↓
[C]
The DHR41B option indicates that the PROFINET IO controller has
not yet established communication.
↓
The PROFINET IO controller is switched off or has not yet been
started up.
[D]
Adapt PROFINET names