6
Electrical installation
Terminal assignment and DIP switches
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
34
NOTICE
The supply voltage must be present on X31:1/2 for using the digital inputs and out-
puts.
Overvoltage may damage the DH.21/41B controller. In this case, the specified func-
tion of the digital inputs and outputs is no longer ensured.
•
To prevent dangerous voltage peaks from occurring, do not connect inductive
loads to the supply voltage or the digital inputs/outputs without free running diodes.
For more information on digital inputs or outputs, refer to chapter
"
75).
6.2.7
X32/X33: CAN 2/CAN 1 system bus interface
Function
Do not connect more than 16 devices to the CAN 1 or CAN 2 system bus. The sys-
tem bus supports the address range 0 to 63.
Connection type
Spring terminal plug connector
CAN 1 wiring diagram
DGND
MOVIDRIVE
MDX60B/61B
X12
SC11 2
1
3
SC12
DHE41B
X3
1
X3
2
X3
3
1
2
3
1
2
3
1
2
3
2
3
1
SC11
DGND
ON
OFF
S12
X12:
2
1
SC12 3
ON
OFF
S12
X45
X46
1 2 3 4 5 6
H L
⊥
FSC11B
MOVITRAC
®
B
S1
OFF
ON
7
S2
X44
®
MOVIDRIVE MDX61B
®
9007201357202827
Assignment: CAN 2 system bus interface (electrically isolated)
No.
Name
Function
X32
1
REF_CAN 2
Reference potential for system bus CAN 2
2
CAN 2H
System bus CAN 2 high
3
CAN 2L
System bus CAN 2 low
22900055/EN – 08/2016