![SEW-Eurodrive DFE32B PROFINET IO Скачать руководство пользователя страница 106](http://html1.mh-extra.com/html/sew-eurodrive/dfe32b-profinet-io/dfe32b-profinet-io_manual_1250328106.webp)
106
Manual – DFE32B Fieldbus Interface PROFINET IO
9
Serial (RS-485) communication via interface adapter
MOVITOOLS® MotionStudio – Operation
9.7.4
Communication parameters, serial (RS-485)
The following table describes the [basic setting] for the serial (RS-485) communication
channel:
The following table describes the [extended setting] for the serial (RS-485) communica-
tion channel:
Communication parameters
Description
Note
COM port
Serial port connected to the inter-
face adapter
•
If there is no value entered
here, the SEW Communica-
tion Server uses the first
available port.
•
A USB interface adapter is
indicated by the addition of
"(USB)".
Baud rate
Transmission speed with which
the connected PC communicates
with the unit in the network via the
communication channel.
•
Possible values:
•
9.6 kBit/s
•
57.6 kBit/s
•
AUTO (default setting)
•
Find the correct value for the
connected unit in the docu-
mentation.
•
If you set "AUTO", the units
are scanned with both baud
rates in succession.
•
Set the starting value for
automatic baud rate detection
under [Settings] / [Options] /
[Communication].
Communication parameters
Description
Note
Parameter telegrams
Telegram with a single parameter
Used for transmitting a
single
parameter
of a unit.
Multibyte telegrams
Telegram with several parameters Used for transmitting the
com-
plete parameter set
of a unit.
Timeout
Waiting time in [ms] that the mas-
ter waits for a response from the
slave after it has sent a request.
•
Default setting:
•
100 ms (parameter tele-
gram)
•
350 ms (multibyte tele-
gram)
•
Increase the value if not all
units are detected during a
network scan.
Retries
Number of request retries after
the timeout is exceeded
Default setting: 3