2

Setra SRPM Room Pressure Monitor                       

The  Setra  SRPM  Room  Pressure  Monitor 

is  designed  for  critical  low 

differential pressure applications that require stringent pressure monitoring 
and alarming. The SRPM can be confi gured to monitor positive, negative 
or neutral pressure in protected environments and hospital isolation rooms 
per CDC guidelines. The SRPM is a complete system that includes a backlit 
RGB LCD display with a graphic user interface, which enables access to 
pressure, security, calibration, and alarm setup. The touch-screen displays 
menus that guide the user through setup, as well as setting up password 
protection. Red and green LED’s and a local audible alarm (with time delay 
feature) alert personnel to system status. The SRPM has a NEMA 1 (IP20) 
rated fi re retardant plastic housing for indoor applications. True differential 
pressure is displayed with a resolution of .0001”. Setra’s patented very low 
pressure  capacitance  sensor  is  dead  ended  and  avoids  the  potential  for 
cross contamination of the room and reference space as well as eliminating 
drift that results from fouling of fl ow based sensors, which by nature have a 
fl ow path connecting the protected and reference spaces. Additionally there 
are 2 levels of password protection available as well as optional BACnet 
MSTP communications.

Содержание SRPM

Страница 1: ...1 Model SRPM Room Pressure Monitor Installation and Operating Manual...

Страница 2: ...that guide the user through setup as well as setting up password protection Red and green LED s and a local audible alarm with time delay feature alert personnel to system status The SRPM has a NEMA 1...

Страница 3: ...m Relay 10 3 3 2 Remote Annunciator 10 3 3 3 Door status input 11 3 3 4 Analog Output 11 3 3 5 BACnet 12 4 0 Startup and Operation 13 4 1 Menu Tree 13 4 2 Power Up 13 4 3 Monitoring Screen 13 4 4 Main...

Страница 4: ...curacy 0 5 F S 0 25 FS optional Operating Temperature Limits 32 to 120 F 0 to 50 C Operating Humidity Limits 5 to 95 Relative humidity non condensing Altitude 2000 meters max Thermal Effects 0 03 F S...

Страница 5: ...network User Interface LCD Display 128 x 128 COG module with custom RGB LED backlight and custom 4 wire resistive touch screen RGB Backlight The SRPM indicates the status of the room being monitored...

Страница 6: ...ity 1 Room pressure snubber Assembly 2 4 Parts required and to be supplied by installer MOUNTING AND WIRING To mount and install properly the following components are required NOT INCLUDED and require...

Страница 7: ...y standard the electrical installer must comply with the following earth ground instructions Pre wire the electrical box with power 24 VAC or 120 240 and provide earth grounding to the electrical box...

Страница 8: ...wiring is 22 AWG stranded wire in a shielded cable a Gnd S and shield should be run This can be 2 twisted pairs with a separate cable shield One twisted pair is used for communications the second twis...

Страница 9: ...male to male barbed tube adaptors onto the end of the tube then push the 4 length silicone tube supplied onto the other end Thread the tubes with installed adaptor through the conduit opening at the...

Страница 10: ...mmon of the internal alarm relay Connect P2 to A1 Located on Remote Annunciator this supplies 15V exc to the Annunciator for powering the circuit during normal conditions Connect P3 of J4 to A2 of SRA...

Страница 11: ...tact closure indicates that the door is closed This is a low voltage circuit 5 VDC Run 2 wires from the door switch to connector J6 on the SRPM See Section 8 0 The door input status function is enable...

Страница 12: ...itch S1 located in the upper right hand section of the PCBA as well as through the touch screen interface see Section 4 4 and 4 9 Position Function 1 MAC address enable 2 N C Not Connected 3 Pull Up R...

Страница 13: ...the screen give you access to the functions that can be performed 4 1 MENU TREE See section 9 0 4 2 POWER UP Apply power and observe the welcome screen and subsequent transition to the pressure monit...

Страница 14: ...password output engineering units and display averaging Room Set up high and low pressure limits to monitor a positive negative or neutral room Operator password setup Alarm Setup latch alarm audible...

Страница 15: ...Change will open Password Setting Screen To change the password enter the present password numeric value followed by the new password in the New Password and Con rm New Password entry boxes then press...

Страница 16: ...ox above the keypad Note The cursor will blink for one to two seconds then stop and display the character Erase any mistakes by using the Back Space key When nished entering data press the Enter key t...

Страница 17: ...e Lower Limit is negative and the Upper Limit is positive the room will be a Neutral Room OPERATOR PASSWORD The operator can only change the room from Occupied to No Isolation and vice versa Lightly p...

Страница 18: ...e alarm resumes This assumes that the room static pressure is still outside the normal or set operating limits The Mute Time Out can be set from 0 to 9999 seconds e Set the Alarm Delay in seconds from...

Страница 19: ...rotected area of the EEPROM memory hasn t been corrupted and also test the alarm to verify the sound level and alarm setup Press Self Test button to initiate EEPROM memory checksum test sequence Press...

Страница 20: ...urate Pressure Calibrator is available apply a steady full scale pressure signal to the on the header tting and press or tap the Span button Reconnect the room pressure tube and calibration is complet...

Страница 21: ...BACnet setup by moving the dip switch position 1 to off left position If the unit will be at the end of the line the pull up resistor can be enabled by pushing position 3 to on The termination resisto...

Страница 22: ...the preset pressure limits the screen turns to yellow Room static pressure outside of the preset limits is indicated by a Red screen after the alarm s time delay expires CHANGING ROOM MODES The SRPM c...

Страница 23: ...med condition occurs i e room pressure falls outside preset range a signal is triggered by the SRPM the green LED shuts off the red LED ashes and the audible alarm sounds The acknowledge button can be...

Страница 24: ...id warranty Be sure to include a brief description of the problem plus any relevant application notes Contact customer service to receive a return goods authorization number before shipping CLEANING I...

Страница 25: ...1 General Requirements Canadian electrical code Part 1 CAN CSA C22 2 No 0 4 04 Bonding of Electrical Equipment CAN CSA C22 2 No 61010 1 04 Safety requirements for electrical equipment for measurement...

Страница 26: ...26 8 0 LOCATION OF COMPONENTS AND ACCESSORIES...

Страница 27: ...27 9 0 MENU TREE...

Страница 28: ...repaired or altered by anyone except SETRA or its authorized service agencies c the serial number or product code has not been removed defaced or otherwise changed and d examination discloses in the...