DPT 264 Series Low Pressure Transducers and Transmitters

Installation Guide

1.0 GENERAL INFORMATION

Every Model DPT264 has been tested and calibrated before shipment. Specific performance specifications are
shown on page 3 of this Guide.

Setra Systems DPT264 pressure transducers sense differential or gage (static) pressure and convert this pressure
difference to a proportional high level analog output for both unidirectional and bi-directional pressure ranges.
Two standard output versions are offered: A voltage output of 0 to 5 VDC or a current output of 4 to 20 mA.

 2.0 MECHANICAL INSTALLATION

2.1Media Compatibility

Model DPT264 transducers are designed to be used with air or non-conducting gases. 

Use with liquids or

corrosive gases will dame the unit.

2.2 Environment

The operating temperature limits of the DPT264 are 0°F to +175°F (-18°C to +79°C)
The compensated temperature range is 0°F to +150°F (-18°C to +65°C).

2.3 Mounting

The DPT264 series is designed for mounting in either 2.75: snap-track or by using the four (4)
slots (suitable for #6 screws) that are provided on the plate.  Optimum performance is obtained by isolating
the instrument from vibration and providing relatively clean, dry ambient air to the pressure ports.

Even though there is no flow through the DPT264, a filter is located in both the high and low-pressure ports
for use in extreme dust or moisture conditions.

In most cases, preferred installation is with the baseplate mounted vertically and located on a relatively flat
surface in a junction box or attached to a nearby beam.  Easy field replacement is possible by removing
the single case screw that holds the black sensor/circuit housing to the baseplate and lifting the black
housing free.  The baseplate remains mounted and can be used with the replacement unit’s black
sensor/circuit housing.

The axis most sensitive to vibration is the one perpendicular to the baseplate.  Avoid mounting with
maximum vibration along this axis.

2.4 Pressure Fittings

The Model DPT264 is designed to be used with 3/16” I.D. push-on tubing. Both the positive (high) pressure
port and the reference (low) pressure port are located on the front of the unit, labeled “HIGH” and “LOW”
respectively. For best results (shortest response time), 3/16” I.D. tubing is suggested for tubing lengths up to
100 feet long, 1/4” I.D. for tubing lengths up to 300 feet, and 3/8” I.D. for tubing lengths up to 900 feet.

3.0 ELECTRICAL INSTALLATION

If the Model DPT264 is supplied with the optional Conduit Enclosure, access the electrical terminations by
removing the cover.

3.1 Voltage Output Units
The Model DPT264 voltage output is a 3-wire circuit, with three terminals available for wiring. These
terminals have the designation COM, EXC, and OUT (see Diagram 1). The power supply and signal
references are commoned on the circuit (see Diagram 2). The DPT264 voltage output can operate from 9-
30 VDC excitation. The DPT264 has a 0-5 VDC output.

Содержание DPT264 Series

Страница 1: ...n extreme dust or moisture conditions In most cases preferred installation is with the baseplate mounted vertically and located on a relatively flat surface in a junction box or attached to a nearby beam Easy field replacement is possible by removing the single case screw that holds the black sensor circuit housing to the baseplate and lifting the black housing free The baseplate remains mounted a...

Страница 2: ...ith a voltage range between 9 and 30 measured between the and terminals The unit is calibrated at the factory with a 24 VDC loop supply voltage and a 250ohm load Current Circuit Diagram Diagram 3 Diagram 4 4 0 CALIBRATION The DPT264 transducer is factory calibrated and should require no field adjustment Generally the mounting position will have a zero effect on ranges below 1 WC Whenever possible ...

Страница 3: ...t between the and terminals and with both pressure ports open to atmosphere the zero may be adjusted by turning the zero adjustment screw See Diagram 3 for location of zero adjustment The factory settings are 4 mA 0 16mA for unidirectional pressure ranges and 12 mA 0 16 mA for bi directional ranges 4 4 Current Output Span Adjustment Span of full scale output adjustments should only be performed by...

Страница 4: ... our Repair Department at 800 257 3872 978 263 1400 for scheduling cost and turnaround estimates MODEL DPT264 PRESSURE PRODUCTS WARRANTY AND LIMITATION OF LIABILITY SETRA warrants its Model DPT264 and CDPT264 products to the original consumer purchaser against defects for a period of three years from the date of sale by SETRA as shown in its shipping documents Without charge SETRA will repair or r...

Отзывы: