Model AXD

Operating Instructions

1.0 Introduction

Every sensor in the AXD product family has been tested and calibrated before shipment. Setra Systems 

AXD product family senses gauge, compound, vacuum gauge and converts this pressure difference 

to a proportional high level analog output. Three standard excitation and output versions are offered:  

Excitation

Output

Output codes

9 to 28 VDC

4-20 mA reverse excitation protection

11

9 to 30 VDC

e.g. 0.5 to 5.5 VDC - (Reverse excitation protection)

24, 2E, et.al

4.9 to 8.1 VDC

Reverse excitation protection 0.5 to 4.5 VDC

45

2.0 Mechanical installation

2.1 Media compatibility

The transducers in the AXD product family are offered with two different types of wetted materials. 

The AXD1 is made with 17-4PH stainless steel and the AXDH is made with 316 stainless steel. Prior 

to use in your application confirm that your media is compatible with the wetted materials of the 

ordered sensor.

2.2 Environment

The operating temperature limits of the AXD are -40° to +257°F (-40 to +125°C) on most electrical 

connection options (except where noted). The compensated temperature range is -4 to +185°F 

(-20 to +85°C).

2.3 Pressure fittings

Typically, standard pipe fittings and procedures should be used. However, for pressure ranges in 

excess of 500 psig, we suggest the use of a sealant such as Locite Hydraulic Sealant. Excessive 

torquing of metal fittings may cause a slight zero shift. The use of plastic fittings typically results in 

no noticeable zero shift. Torquing does not appreciably affect linearity or sensitivity.

2.4 Venting

Because the reference pressure in a sealed gauge transducer will vary due to changes in temperature 

and will affect overall accuracy (especially in units of less than 200 psig range), all transducers in the 

AXD product family are available in both vented or sealed pressure types.
Vented units are ordered as gauge pressure type (e.g. PSIG) units. Sealed units are ordered as 

sealed gauge type (e.g. PSIS) range units. The AXD gauge transducers  are vented through electrical 

termination as shown in table below.

Electrical termination

Venting

Cable (XX)

Venting through cable

3-pin packard (P1)

Venting through porous filter protected by loose o-ring

M12, 4-pin (M4)

Venting through connector

Terminal strip/conduit ("A1")

Venting through porous filter on terminal strip

3.0 Electrical installation

The AXD product family is available with four electrical terminations:

•  (2ft/0.5m, 6ft./2m, 12ft/4m, 25ft/8m) cable

•  M12-4 PIN connector

•  3-pin packard connector

•  Terminal connection w/ conduit adapter, 1/2 inch

Содержание AXD

Страница 1: ...ly standard pipe fittings and procedures should be used However for pressure ranges in excess of 500 psig we suggest the use of a sealant such as Locite Hydraulic Sealant Excessive torquing of metal fittings may cause a slight zero shift The use of plastic fittings typically results in no noticeable zero shift Torquing does not appreciably affect linearity or sensitivity 2 4 Venting Because the re...

Страница 2: ...ative Model AXD Setra transducer 4 20 mA Power supply Load monitor _ _ _ CAUTION Reverse excitation will not cause damage to the unit unless voltage applied is above 50 VDC However the unit will not function if reverse wired Red Excitation Black Excitation Monitor or Control Device _ Green Out White Out Shield Out Out Model AXD Setra transducer Voltage Output Voltage Current output 3 2 Output wiri...

Страница 3: ...sten the wires to terminals 3 Screw on the Model AXD top cover Hand tighten only 2Lb Ft 3N m max torque 4 Fit conduit into conduit fitting and tighten conduit liquid tight strain relief 3 4 EMC Certification This product complies with EN61326 electrical equipment for measurement control and laboratory use EMC requirements for minimum requirements and industrial locations Special caution should be ...

Страница 4: ...ill repair or replace products found to be defective in materials or workmanship within the warranty period provided that a the product has not been subjected to abuse neglect accident incorrect wiring not our own improper installation or servicing or use in violation of instructions furnished by SETRA b the product has not been repaired or altered by anyone except SETRA or its authorized service ...

Отзывы: