WOOD BOILER INSTRUCTIONS   Page 1                                                                                     Copyright ©  2011  Seton Wood Boilers   all rights reserved 

NEVER OPERATE WITH THE FEED DOOR OPEN!! 

THE SETON BOILER MUST BE INSTALLED IN A ENCLOSED, INSULATED ROOM. 

IT SHOULD BE REMOTE FROM THE LIVING SPACE.

 

Installation and Operation Instructions for 

W-90E   W-130E  W-180E 

 

SAFETY INSTRUCTIONS 

Safety Notice:  If this is not properly installed, a house/building fire may result.  For your 
safety,  contact  local  building  or  fire  officials  about  permits,  restrictions,  and  installation   
requirements for your area.   

NEVER BLOCK DRAFT IN OPEN POSITION 

Do not open the feed door until the wood has burned down some. 

Avoid trying to see how the fire is burning shortly after you fill it. 

All wood burning appliances will smoke if you open the feed door  

when it is full of wood.  

Do not over-fire the boiler.   

Over-firing will occur if the feed door is left open  

or the draft is blocked open during operation.  

 Such actions can result in very dangerous operating conditions. 

Because of the very high efficiency of the Seton boiler the flue gas exhaust temperatures 

can be low enough to cause condensation in the chimney. This condensation may, over 

time, damage a masonry chimney. If you have condensation in your chimney, a insulated 

stainless steel chimney liner should be installed inside the flue

 

SETON WOOD BURNING PRODUCTS 
406-295-9902              24 RIVERVIEW DR.   TROY MT 59935 

Seton Wood Boilers       

Seton Wood Boilers       

Seton Wood Boilers       

There is no substitute for doing it right.

There is no substitute for doing it right.

There is no substitute for doing it right.

There is no substitute for doing it right.

    

PLUMB BOTH RELIEF VALVES TO A SAFE LOCATION 

PIPE MUST RUN DOWN HILL ITS FULL LENGTH. PLUMB TO AN OUTSIDE AREA., DO NOT 

 ALLOW THE PIPE TO EXTEND OUTSIDE FAR ENOUGH TO FREEZE. O NOT REDUCE THE PIPE SIZE. 

DO NOT PUT THREADS ON THE OPEN END OF THE DRAIN PIPE  

DO NOT JOIN THE TWO DRAINS TOGETHER 

 

WARNING!! ATOMIZED POLYPROPYLENE GLYCOL AT  

HIGH TEMPERATURES CAN CAUSE AN EXPLOSION!!  

Содержание W-130E

Страница 1: ...locked open during operation Such actions can result in very dangerous operating conditions Because of the very high efficiency of the Seton boiler the flue gas exhaust temperatures can be low enough...

Страница 2: ...owever please keep this certificate for your records as required by the IRS Please consult your tax professional to determine if you are eligible for this credit The following Biomass Burning Stoves a...

Страница 3: ...s always available to it and that if the T P relieves water because of a high water temperature the cold fill water will flow up through the boiler to cool it The Seton Boiler is not designed to be in...

Страница 4: ...S 25 30 POWER FAILURES 25 WIRING 26 29 BACKUP POWER 25 BOILER BUILDING 62 63 PLUMBING ARRANGEMENTS 31 54 TROUBLE SHOOTING 66 PLUMBING TO REMOVE AIR 47 UNDERGROUND 56 57 OFF GRID HEATING 64 MAINTENANCE...

Страница 5: ...NSTRUCTIONS Page 5 Copyright 2011 Seton Wood Boilers all rights reserved BOILER INSTALLATION DRAFT MOTOR PROTECTOR PROTECTOR PLATE INSTALL TWO SCREWS 3 INCHES THIS PLATE PROTECTS THE DRAFT MOTOR FROM...

Страница 6: ...opyright 2011 Seton Wood Boilers all rights reserved BOILER INSTALLATION HINGE OILING THE DOOR HINGES MUST BE OILED ONCE A MONTH WITH A MOTOR OIL IT ONLY TAKES A COUPLE OF DROPS THERE IS A SMALL HOLE...

Страница 7: ...BY THE EXHAUST AFTER ALL THE HEAT IS REMOVED BY THE WATER CROSS DRAFT KEEPS THE ASH IN THE FIRE BOX NOT IN THE AIR EXHAUST EXITS HERE NORMALLY BELOW 300 DEGREES INDICATING A VERY HIGH EFFICIENCY HEAT...

Страница 8: ...eserved BOILER INSTALLATION PARTS IDENTIFICATION EXPANSION TANK DRAFT MOTOR WATER TO HEATING WATER FROM HEATING EXHAUST CIRCULATING PUMP TACO 008 FLOAT VENT 30 POP OFF 12 FILL VALVE POWER CORD T P VAL...

Страница 9: ...PRESSURE RELIEVE VALVE AUTO AIR VENT When the boiler is plumbed this way it is protected from over temperature When the T P valve releases because of over temp the cold water will come up through the...

Страница 10: ...ROM BOILER POWER CORD 11O VOLTS 100 WATTS DRAFT MOTOR OPENS AND CLOSES DRAFT TO CONTROL WATER TEMPERATURE ANTIFREEZE ANTIFREEZE IS CORROSIVE AND WILL SHORTEN THE LIFE OF YOUR BOILER IF NOT MAINTAINED...

Страница 11: ...ial type or building heating appliances which burn solid fuel The boiler is designed to operate in either a parallel arrangement with the central boiler or as a boiler by itself BOILER DESCRIPTION INS...

Страница 12: ...nspect the chimney connector and chimney once monthly during the heating season and clean if necessary 9 To prevent injury do not allow anyone to use this boiler who is unfamiliar with the correct ope...

Страница 13: ...with boiler maintain ing proper clearances Seal the flue pipe in the chimney with furnace cement Chimney connections must be securely supported and joints fastened with sheet metal screws or rivets 5...

Страница 14: ...IMNEY CAP Use 8 round stove pipe Secure each pipe section and or elbow joint with three 3 sheet metal screws per joint to firmly hold the sections together Re check clearances from the boiler connecto...

Страница 15: ...bove the roof and be at least two 2 feet higher than any point of the roof within ten 10 feet NOTE A draft reading of 0 06 to 0 07 W C Water Column is required for proper burning of this boiler CREOSO...

Страница 16: ...ter a device that measure draft 1 Close all windows and doors in the building and turn on all appliances that remove air from the home e g heat pump air conditioner exhaust fan clothes dryer fireplace...

Страница 17: ...ghts reserved This chimney has three 90 degree bends plus two 45 degree bends a total of 360 degrees plus a 2 inch reduction all in single wall pipe This will not draw properly it will need a draft in...

Страница 18: ...s only as necessary Elbows reduce draft no more than two should be used in any chimney 3 Make sure all horizontal runs of connector pipe have a minimum outward rise of 1 4 per hori zontal foot This al...

Страница 19: ...oof and be at least two 2 feet higher than any point of the roof within ten 10 feet If you have any questions regarding venting your boiler contact the manufacturer or contact the National Fire Protec...

Страница 20: ...at the ceiling you will need enough 8 round black stove pipe to reach the ceiling The top of the chimney must be at least three 3 feet above the roof and be at least two 2 feet higher than any point...

Страница 21: ...The use of more than two 90 deg bends may decrease the amount of draw and possibly cause smoke spill age Where possible use only corrugated non adjustable elbows These are much more airtight The chimn...

Страница 22: ...WARNINGS NEVER BLOCK DRAFT IN OPEN POSITION NEVER OPERATE WITH FEED DOOR OPEN ANTIFREEZE Do no install antifreeze in the boiler for a few weeks in case of boiler problems that would blow the antifreez...

Страница 23: ...oke escaping from the door When adding fuel put logs in crosswise place logs on door frame and roll into the fire box Do not put logs into firebox that are longer than the door opening Do not put logs...

Страница 24: ...RY IT CAN CAUSE A WEDGE TYPE FORCE ON THE BACK PIECE OF REFRACTORY IF IT IS TOO LONG IT WILL CAUSE THE REFRACTORY IN THE DOOR TO CRACK END FIRST ALSO REQUIRES YOU TO THROW THE WOOD AGAINST THE BACK TH...

Страница 25: ...rature by closing the draft with an increase in water temperature and opens the draft when the water temperature drops The differential should be set at 15 degrees Set auxiliary aquastat at 190 to 200...

Страница 26: ...E BOX WHEN THE DRAFT CLOSES AND THERE IS NO SECONDARY CIRCULATION THE PRIMARY CIRCULATION IS THE WATER IN THE BOILER THAT CIRCULATES THROUGH THE BOILER AND HEAT EXCHANGER THE SECONDARY CIRCULATION IS...

Страница 27: ...VOLTAGE AND BY PASSES THE THERMOSTAT ON YOUR LARGEST HEATING ZONE THE SETON BOILER REQUIRES SOME MEANS OF KEEPING THE PUMP FROM CIRCULATING WA TER WHEN THERE IS NO HEAT OR FIRE IN THE BOILER THIS KEEP...

Страница 28: ...BE A HIGH VOLTAGE STAT OR A RELAY CONTROLLED BY YOUR THERMOSTAT SYSTEM THE CIRCULATING PUMP RUNS CONTINUALLY DRAFT MOTOR 110 VOLTS B W DRAFT 180 R B WIRING DIAGRAM AQUASTAT OPERATION Single Zone Shop...

Страница 29: ...opyright 2011 Seton Wood Boilers all rights reserved PLUMBING RADIANT SYSTEM WIRING AN INVERTER FOR BACKUP DPDT RELAY 120 VOLT COIL INVERTER 1000 WATTS AUTOMATIC CHARGER BATTERY BOILER AND PUMPS 500 W...

Страница 30: ...e and replace with a 3 4 brass nipple 3 4 brass tee PLUMBING WATER HEATER POP OFF BRASS TEE COPPER PIPE TO TOP OF HEAT EXCHANGER FAUCET BRASS TEE COPPER PIPE TO BOTTOM OF HEAT EXCHANGER VERY SMALL BRO...

Страница 31: ...N COIL PLUMBING FAN COIL IN A FORCED AIR SYSTEM RETURN LINE MUST COME OUT OF TOP OF EXCHANGER TO PREVENT TRAPPING AIR PLUMBING RADIANT SYSTEM STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL HEAT EXCHAN...

Страница 32: ...OUSE SHOP POOL BOILER FAN COIL PUMP FEEDING SHOP SHOULD BE WIRED TO PUMP ON WOOD BOILER THERMOSTAT IN SHOP WILL TURN FAN COIL FAN ON AQUASTAT ON SUPPLY TO FAN COIL WILL TURN FAN ON AT 200 DEGREES PUMP...

Страница 33: ...OLD RETURN HEATING There are several ways you can plumb the Seton boiler into your present heating system Here some of the ways that work well I will furnish drawings with each sale to make it sim ple...

Страница 34: ...EITHER PLACE OUT FOR HEATING COLD RETURN HEATING There are several ways you can plumb the Seton boiler into your present heating system Here some of the ways that work well I will furnish drawings wi...

Страница 35: ...ER Circulating pump SETON BOILER SMALL BRONZE CIRCULATING PUMP HEAT EXCHANGER DRAIN VALVE FAN COIL INSTANTANEOUS WATER HEATER Circulating pump STORAGE TANK FLOAT VENT TACO 0011 FLOAT VENT SETON BOILER...

Страница 36: ...ter heating plus radiant PLUMBING WATER HEATER FORCED AIR RADIANT WATER HEATER Circulating pump SETON BOILER SMALL BRONZE CIRCULATING PUMP HEAT EXCHANGER DRAIN FAN COIL EXPANSION TANK 12 REGULATOR FIL...

Страница 37: ...losed boiler system with a closed forced air system and extra fan units Circulating pump SETON BOILER CHECK VALVE FAN COIL EXPANSION TANK 12 REGULATOR FILL VALVE RETURN AIR VENT FURNACE MOTOR LOW VOLT...

Страница 38: ...g pump VALVE DRAIN VALVE FAN COIL SETON BOILER SETON BOILER A simple closed forced air system A simple open forced air system VALVE DRAIN VALVE FAN COIL PLUMBING WATER HEATER RADIANT AIR VENT AIR VENT...

Страница 39: ...N BOILER Circulating pump BOILER 2 BOILER 1 CHECK VALVE CHECK VALVE TO HEATING SYSTEM TO HEATING SYSTEM FROM HEATING SYSTEM FROM HEATING SYSTEM A Seton boiler feeding two boilers You will need an air...

Страница 40: ...OPS EXISTING BOILER CIRCULATING PUMP Hooking the Seton Boiler to an existing boiler With the heat exchanger PLUMBING INTO ANOTHER BOILER Connecting the Seton Boiler to an existing boiler without the h...

Страница 41: ...41 Copyright 2011 Seton Wood Boilers all rights reserved HEATING LOOPS HEATING LOOPS EXISTING BOILER CHECK VALVE CIRCULATING PUMP Hooking the Seton Boiler to an existing boiler With the heat exchanger...

Страница 42: ...CALD VALVE FOR DOMESTIC WATER RADIANT SUPPLIES RADIANT RETURNS 3 4 PEX WATER HEATER SMALL SS CIRCULATING PUMP HOT OUT TO DOMESTIC COLD IN DOMESTIC SETON BOILER VALVE DRAIN VALVE EXPANSION TANK FILL VA...

Страница 43: ...OMESTIC WATER HEATING PLUMBING CLOSED RADIANT AND WATER HEATER CIRCULATING PUMP INSTALL ANTI SCALD VALVE FOR DOMESTIC WATER RADIANT SUPPLIES RADIANT RETURNS 3 4 PEX WATER HEATER SMALL BRONZE CIRCULATI...

Страница 44: ...INSTRUCTIONS Page 44 Copyright 2011 Seton Wood Boilers all rights reserved SETON BOILER TACO 0011 OR 008 BRASS UNIT HEATER UNIT HEATER UNIT HEATER UNIT HEATER PLUMBING WOOD BOILER TO UNIT HEATERS HEA...

Страница 45: ...6 917 Well L37 829 NO 2 120 V ELEMENT NO 1 120 V ELEMENT NO NO 110 VOLT 20 AMP 24 V COIL 110 VOLT 20 AMP 24 V COIL CONTROL PANEL END SWITCH CR OR C 30 A DPST NO RELAYS 24 V COILS COM COM COM COM NO NO...

Страница 46: ...STAT L4006A1145 L36 917 Well L37 829 NO 2 120 V ELEMENT NO 1 120 V ELEMENT NO NO 110 VOLT 20 AMP 24 V COIL 110 VOLT 20 AMP 24 V COIL CONTROL PANEL END SWITCH CR OR C 30 A DPST NO RELAYS 24 V COILS CO...

Страница 47: ...AIR AIR WILL NOT GO DOWN ANY PLACE THE WATER TURNS DOWN PLACE AN AIR VENT THE BEST ONES ARE CALLED FLOAT VENTS AND ARE AUTOMATIC REMOVING AIR FROM A HYDRONIC SYSTEM VENT NEEDED HERE REMOVING AIR FROM...

Страница 48: ...OILER AND BACKUP TAKAGI ALL PLUMBING MUST BE PEX OR COPPER OR BRASS NO CAST IRON OR GALVANIZED OR STEEL INSULATED STORAGE TANK TACO 008 SS PUMP SWING CHECK VALVE R R ADIANT ADIANT D D ESIGN ESIGN I I...

Страница 49: ...IANT ADIANT D D ESIGN ESIGN I I NSTITUTE NSTITUTE C C OM OM 1 1 406 406 295 295 9902 9902 Quality by Design WOOD BOILER ANTISCALD VALVE HOT DOMESTIC OUT 0011 TACO PUMP INSTANT WATER HEATER COLD IN 008...

Страница 50: ...IANT ADIANT D D ESIGN ESIGN I I NSTITUTE NSTITUTE C C OM OM 1 1 406 406 295 295 9902 9902 Quality by Design WOOD BOILER ANTISCALD VALVE HOT DOMESTIC OUT 0011 TACO PUMP INSTANT WATER HEATER COLD IN 008...

Страница 51: ...GN I I NSTITUTE NSTITUTE C C OM OM 1 1 406 406 295 295 9902 9902 Quality by Design WOOD BOILER ANTISCALD VALVE HOT DOMESTIC OUT 0011 TACO PUMP INSTANT WATER HEATER COLD IN CHECK VALVES M C CLOSED DOME...

Страница 52: ...NTI SCALD VALVE FOR DOMESTIC WATER TACO 008 or 0011 IRON PUMP INSULATED INDIRECT WATER HEATER TAKAGI INCOMING COLD ALL PLUMBING MUST BE PEX OR COPPER OR BRASS NO CAST IRON OR GALVANIZED OR STEEL 1 INS...

Страница 53: ...H MIXING VALVE TO AND FROM RADIANT HEAT Plumb from heater to tank with 3 4 copper or pex SS TACO 008 1 BRASS FLANGES ALL PLUMBING MUST BE PEX OR COPPER OR BRASS NO CAST IRON OR GALVANIZED OR STEEL AQ...

Страница 54: ...ventilating in cold weather isn t an energy wasting practice The fact is most heated homes will leak some air due to pressure differences and the natural stack effect of the house Stack Effect means...

Страница 55: ...O 3 FT IS GOOD 2 INSTALL THE 4 CORRUGATED PIPE IN THE BOTTOM OF DITCH WITHOUT PEX 3 FILL THE DITCH UP TO THE TOP OF THE CORRUGATED PIPE AND COMPACT 4 COVER THE CORRUGATED PIPE WITH INSULATION 5 FINISH...

Страница 56: ...ade Easy Do it Yourself Soythane is a Do It Yourself DIY Spray in Place Urethane Foam The use of Bio renewable energy allows you to use renewable energy to save energy Soythane is a DIY Do It Yourself...

Страница 57: ...s pumps pressure reducing valves and pop offs Failure to follow the instructions furnished with the Seton boiler will void the warrantee Some of the things that are not covered are Burning fuels that...

Страница 58: ...er Step 1 Address and remove existing scale deposits if any exist following directions and dosages for Scale Out Solution FLUSH THOROUGHLY Step 2 Clean and passivate system with required amount of Pre...

Страница 59: ...or completely filled the water will have to be drained off Turn the boiler off and attach a hose to the drain valve of the expansion tank Close the valve that connects the expansion tank to the boiler...

Страница 60: ...set point is normally an external control to the boiler It controls the temperature of the circulating water This can be a fixed setpoint set around 160 F to 180 F Outdoor reset controls are not reco...

Страница 61: ...right 2011 Seton Wood Boilers all rights reserved IF YOU DO NOT HAVE AN OUT SIDE BUILDING FOR THE BOILER THIS IS A PLAN YOU COULD USE FOR THE BOILER AND WOOD STORAGE SIDE VIEW TOP VIEW BOILER CHIMNEY...

Страница 62: ...WOOD BOILER INSTRUCTIONS Page 62 Copyright 2011 Seton Wood Boilers all rights reserved BACK FRONT 8 to 12 BOILER BUILDING...

Страница 63: ...is a sign that fresh water is coming into the system from fresh makeup water This problem is caused from leaks in the system or the boiler blowing water out the relief valves from improper aquastat se...

Страница 64: ...open Reduce speed of optional draft inducer Damper actuator stuck open or defective Aquastat set points incorrect Aquastat defective Pressure Buildup in System Pressure relief valve actuation Gage sh...