Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Displaying user outlet, group and serial port access:
The List User command displays all accessible outlets, groups and serial ports for a user.
To display user outlet, group and serial port access:
At the Switched -48 VDC: prompt, type
list user
, optionally followed by a username. Press
Enter
.
Example
The following command displays information about the user JaneDoe:
Switched -48 VDC: list user janedoe<Enter>
Username: JANEDOE
Outlet Outlet
ID Name
.AA1 DataServer_1
.AA2 WebServer_1
Groups:
ServerGroup_1
ServerGroup_2
More (Y/es N/o): Y
Ports:
Port Port
ID Name
Console Console
Modem Modem
JaneDoe can access the following outlets, groups and serial ports: outlet A1 which has a descriptive name of
DataServer_1, outlet A2 which has a descriptive name of WebServer_1, group ServerGroup_1 group ServerGroup_2,
Console serial port and Modem serial port.
Outlet Administration
Setting the reboot delay:
The Set Outlet RebootDelay commands sets the reboot delay for all outlets.
To set the sequencing interval:
At the Switched -48 VDC: prompt, type
set outlet rebootdelay all
, followed by a value from 5 to 600 (in seconds) and
press Enter.
Creating a descriptive outlet name:
The Set Outlet Name command assigns a descriptive name to an outlet. You can use this name in commands that
require an outlet name as an alternative to using the outlet’s absolute name.
To create an outlet name:
At the Switched -48 VDC: prompt, type
set outlet name
followed by the absolute outlet name, then a descriptive name
of up to 24 alphanumeric and other typed characters - (ASCII 33 to 126 decimal) are allowed; spaces are not allowed;
outlet names are not case sensitive. Press
Enter
.
Example
The following command adds the descriptive name DataServer_1 to outlet .aa1:
Switched -48 VDC: set outlet name .aa1 DataServer_1<Enter>