26
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Interfaces
The -48 VDC Remote Power Manager has two interfaces: the Web interface accessed by the HTTP enabled Ethernet
connections, and the Command Line Interface (CLI) for serial and Telnet connections.
Outlet Naming and Grouping
For commands requiring an outlet name, you can specify it in one of two ways: a predefined absolute name or a
descriptive name assigned by an administrator.
For units with multiple infeed connectors, absolute names are specified by a period (.) followed by the tower letter, the
infeed letter and outlet number.
Example
:
The absolute name for outlet 8 on the B infeed of tower A is .AB8.
Outlets can also be included in one or more named groups of outlets, allowing you to issue a command that affects all
outlets in a named group.
Usernames and Passwords
The -48 VDC Remote Power
Manager has one predefined administrative user account (username/password: admn/admn), and
supports a maximum of 112 defined user accounts.
NOTE:
For security, Server Technology recommends removal of the predefined administrative user account after a new account with
administrative rights has been created.
Only an administrative-level user can perform operations such as creating/removing user accounts and command access,
changing passwords and displaying user information. An administrator can also view the status of all sensors and power
inputs.
Usernames can contain from 1-16 characters and are not case sensitive; spaces are not allowed. Passwords can contain
up to 16 characters, and are case sensitive.