Data Pro
P/N 10029355 Rev AE
Operation Manual
Page 11 of 92
Figure
4
– Peripheral Connections
ID #
Connector
Description
Torque
(in-lbs)
1
J14, J15
Alarm/Relays
5
2
JP5, JP6, JP7
Analog input voltage/current selection
N/A
3
J13
Analog input
– 3 channels
2
4
J12, J10
Analog outputs
– 2 channels
2
5
J5, J7
DC power input
5
6
ST1
Earth ground screw for input power
8
7
J2, J3
Power connection for SPS or FIC’s
2
8
J6
COM3
– RS-485 Modbus slave
2
9
J8
COM2
– RS-232 Modbus slave
2
10
J11
COM5
– Reserved for SPS/FIC Modbus Connection
2
11
J17, J16
COM1
– RS-232/RS-485 Modbus port
2
Table
4
- Peripheral Connections
3.1 Analog Input
The analog inputs (port J13) are configurable for voltage or current measurements via jumper
placement. Measured values are displayed on the Data Pro main screen and logged into the *.csv file.
The analog inputs are available as parameters for further processing with other options such as
graphing, relay configurations, and 4-20mA configuration.
shows the placement of jumpers for
three analog input channels.
9
10
8
6
1
2
3
4
5
7
11