INSTALLATION INSTRUCTIONS

DESCRIPTION

: CL/19 is a level control for conductive liquids, modular enclosure (35 mm) for 46277 DIN rail.

Selection of detection sensitivity (HIGH - LOW) and functions (FILLING o DRAINING ) via microswitches.
The low alternate current applied on the sensors guarantees safety of the CL/19 and eliminates the
undesired effects of electrolysis.

SR 15.19

230V

~

SR 15.49

110V

~

SR 15.59

24V

~

WARNING: CL/19 does not work with: DISTILLED WATER, OILS, HYDROCARBONS,

LOW CONDUCTIVITY LIQUIDS.

WIRING DIAGRAM

Microswitch 2

for selection

High sensitivity (ON)

Low sensitivity (OFF)

Microswitch 1

for selection

g (ON)

Filling (OFF)

Drainin

Relay status indicator

= energised on filling

or draining

On

Off

= de-energised CL/19 on standby

GREEN LED

The following SERAI sensors can be
connected to the CL/19: R/1, R/2, R/4,
R/5, R/40, R/3A, R/3B and R/6.

If the tank is in conductive

material, terminal C (common) can be
connected directly to the tank.

WARNING:

SR 15.19 230 ÷ 240V ±10% 50/60Hz

~

SR 15.49 110 ÷ 125 V ±10% 50/60Hz

~

SR 15.59 24 V ±10% 50/60Hz

~

Flashing

= sensors in short circuit

Off

= mains power off

On

= mains power present

Mains power indicator led

SINCE

1965

The CL/19 is equipped with a top quality relay suitable
for virtually all applications. However, the use of
contactors is recommended to control motors with an
output higher than the specified values.

1

2

CL/19

ON

2

SELEZIONE SENSIBILITÀ

SENSITIVITY ADJUSTMENT

2

ON

ON

BASSA

ALTA

LOW

HI

CONTROLLO LIVELLO IN

LEVEL CONTROL

1

ON

1

ON

RIEMPIMENTO

FILLING

SVUOTAMENTO

EMPTYING

RED LED

Motors and pumps: 8A@230V

~

max ½ HP

35 X 90 X 70.5mm / 144 g.

IP 20 for terminals

Power supply:

12mA - 230V

~

Consumption on standby: ........................

1 changeover

Relay output: ............................................

Resistive: 10A @230V

~

Applicable load: ........................................

9V

~

Voltage on sensors: .................................

0,9mA Max

Current absorption of immersed sensors:

3 seconds

Activation threshold: ................................

-10 ÷ +60°C

Operating temperature: ...........................

Protection rating: .....................................

Insulation class: .......................................

Dimensions and weight: ..........................

If correctly installed, the device has no accessible parts.

SR 15.69

400V

~

SR 15.69 400 ÷ 415V ±10% 50/60Hz

~

m

C

A1

A2

M

NC NO

11

12

14

F

N

SR 15.19

230V~

SR 15.49

110V~

SR 15.59

24 V~

SR 15.69

400V~

C m M

E3

E2

E1

Maximum

cable length

250 m.

Section 1mm²

F / R

N / S

*

*

*

( R)

( )

( S)

-20 ÷ +70°C

Storage temperature: ...............................

95% condensate-free

Max. relative humidity: .............................

LEVEL CHECK OF CONDUCTIVE LIQUIDS

FOR FILLING OR DRAINING

CL/19

IP 40 for front panel

SINCE

1965

WARNING: If the
controlled liquid shows,
at the operating
temperature, fumes or
condensation, it is
recommended not to
use sensors with the
terminals close to each
other such as sensors
R/1 and R/2.

The condensing
humidity can cause a
bad working of the
level control.

If that is the case, it is
suggested to install
single sensors spaced,
see R/3A, R/4, R/5, R/6,
R/40 etc.