Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
142
System Manual, 09/2009, A5E02316180B-02
SUBPERIOD #
Number of subperiods
Range: 1 to 5
Default value: 1
The number "1" defines the fixed block method.
The numbers "2" to "5" define the rolling block method.
SYNC. SOURCE
Source of the synchronization pulse for synchronizing the load
profile recording.
Range: NONE, BUS, DIG. INPUT, INT. CLOCK
NONE
Synchronization is switched off.
BUS
Synchronization via the
communication interfaces.
DIG. INPUT
Synchronization via the digital
input.
INT. CLOCK
Synchronization via the internal
clock.
Default value: INT. CLOCK
For synchronization via the digital input, the digital input must
previously be parameterized for this purpose. ("SETTINGS >
INTEGRATED I/O > DIGITAL INPUT", Field "ACTION", value
"DEMAND SYNC"). The "SYNC. SOURCE" field is
automatically reset to "NONE" if another function is assigned
to the digital input.
See also
9.2.6
Date / time
Device settings relating to the date and time.
Call: "SETTINGS > DATE/TIME"
Figure 9-6
"DATE/TIME" device settings