Startup
7.3 Parameterizing the device
SENTRON PAC4200
106
System Manual, 09/2009, A5E02316180B-02
7.3.4
Voltage input
7.3.4.1
Set the connection type
Inform the device of the connection type executed. To do so, enter the short code for the
connection type in the device settings.
Note
Connection type
The connection type executed must agree with the connection type entered in the device!
Table 7- 2
Available connection types
Short code
Connection type
3P4W
3 phases, 4 conductors, unbalanced load
3P3W
3 phases, 3 conductors, unbalanced load
3P4WB
3 phases, 4 conductors, balanced load
3P3WB
3 phases, 3 conductors, balanced load
1P2W
Single-phase AC
You can find further information on the possible connection types, and on how the measured
value representation depends on the connection type, in the "Description" chapter.
Procedure
1.
Exit the measured value display and call the "MAIN MENU":
<F4>
2.
In the main menu, go to the "SETTINGS" entry:
<F2>
or <F3>
3.
Call the "SETTINGS" entry:
<F4>
4.
In the "SETTINGS" menu, go to the "BASIC PARAMETERS" entry:
<F2>
or <F3>
5.
Call the "BASIC PARAMETERS" entry:
<F4>
6.
In the "BASIC PARAMETERS" menu, call the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
Figure 7-4
"CONNECTION TYPE" device setting
Содержание PAC4200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC4200 16 System Manual 09 2009 A5E02316180B 02 ...
Страница 66: ...Operation planning 4 1 Operation planning SENTRON PAC4200 66 System Manual 09 2009 A5E02316180B 02 ...
Страница 174: ...Service and maintenance 10 6 Disposal SENTRON PAC4200 174 System Manual 09 2009 A5E02316180B 02 ...
Страница 284: ...Index SENTRON PAC4200 284 System Manual 09 2009 A5E02316180B 02 ...