Sentex Ovation S Скачать руководство пользователя страница 4

Rev B

Doc.  6001072

Page 3 of 28

BASIC INSTALLATION RULES

PLEASE READ THIS SECTION VERY CAREFULLY BEFORE BEGINNING YOUR INSTALLATION.

In the sections that follow, detailed procedures are discussed for each step required to install the

Ovation system. In addition to these specific procedures, there are general rules which will help ensure
that your installation is done correctly and efficiently:

1. GROUND THE SYSTEM.

  The Ovation system contains parts which may be damaged by static

discharge.  This type of damage is not covered by Sentex's warranty.  A proper earth ground
connected to the controller and LIB housings at the grounding points shown in Figures 12 and
14

 

will significantly reduce the chances of damage or improper operation.  The shields in the

cables specified for all remote sensors and controls should also be connected to earth ground
at the point shown in Figure 12.
To be effective, the ground connection must be made by running 12 AWG copper wire to a
good ground point (e.g., an electrical panel, a metallic cold water pipe that runs into the earth,
or a grounding rod at least 10 feet in length that is driven into the earth) within 12 feet of the
system.  If you cannot meet these requirements, a ground will be of little value.  Even if you
have a good earth ground, you should still try to discharge any static electricity before handling
the circuit boards.

2. PROVIDE POWER FROM A DEDICATED SOURCE

.  The outlet(s) into which you plug the

transformers provided, or a DC power supply, should be wired to their own circuit breaker.  This
will reduce the line noise introduced into system power and minimize the risk of having other
equipment interrupt system operation.  Additionally, each Ovation controller, LIB housing, and
door strike must have their own individual transformer.

3. DO NOT OVERLOAD THE TERMINAL BLOCKS

.  The terminal blocks used in the Ovation

system are unpluggable and the pins are soldered into the boards.  To connect your wires,
remove the "head" from the correct terminals and open the screws.  Insert the wire into the
correct opening on the front and tighten the screw until the wire is held snugly.  When you have
made all connections for a given "head," plug it back onto the pins designated for that terminal
block.

Stranded wire must be between 16 and 24 AWG.  Solid wire must be between 18 and 24 AWG.
This is the total thickness measurement, so if you are putting two wires in together, the
combined thickness must fall within this range.  

NEVER

 try to insert more than two wires per

terminal.

4. ENSURE GOOD CONNECTIONS

.  A light tug on the wire will tell you if the connection is

secure.  When reconnecting system components, make sure all pins are straight on chips,
connectors, and terminal block heads.

5. READ THE MARKINGS CAREFULLY

.  The connection points are marked on the boards

clearly.  Before making any connection, be sure to read the marking and check it against the
corresponding figure in these instructions so that you understand the connection you are
making.

6. TRAIN YOUR CUSTOMER

.  The Ovation system is very simple to program and use once a

short learning period has been completed.  However, untrained programmers can cause
serious problems for you and themselves.  Ensure your customer has a copy of the manual
Programming and Use Instructions for all Ovation Systems (Doc. No. 6001012) to guide them.
SPEND TIME NOW to train your customer on proper use of the system.  It will save you and
them a lot of aggravation and inconvenience later.

Содержание Ovation S

Страница 1: ... B Rev B INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FOR THE FOR THE FOR THE FOR THE S S S S AND AND AND AND V V V V MODEL MODEL MODEL MODEL OVATION SYSTEMS OVATION SYSTEMS OVATION SYSTEMS OVATION SYSTEMS ...

Страница 2: ...hen you are installing the system or making changes to the system configuration TABLE OF CONTENTS BASIC INSTALLATION RULES 3 PART 1 SYSTEM OVERVIEW 4 1 OVATION CONTROLLER 4 2 LINE INTERFACE BOARDS LIBs 4 PART 2 SAMPLE INSTALLATION 6 1 SINGLE ENTRANCE 6 2 MULTIPLE ENTRANCES 7 PART 4 PHONE LINE INSTALLATION 8 1 ARRANGING TELEPHONE INSTALLATION 8 2 INSTALLING RJ71C JACKS 8 3 LIB PLANNING FORM 9 PART ...

Страница 3: ...reserves the right to make changes in the products described in this manual without notice and without obligation of Sentex to notify any persons of any such revisions or changes Additionally Sentex make no representations of warranties with respect to this manual This document is protected by copyright and may not be copied or adapted without the prior written consent of Sentex Systems This docum...

Страница 4: ...ing other equipment interrupt system operation Additionally each Ovation controller LIB housing and door strike must have their own individual transformer 3 DO NOT OVERLOAD THE TERMINAL BLOCKS The terminal blocks used in the Ovation system are unpluggable and the pins are soldered into the boards To connect your wires remove the head from the correct terminals and open the screws Insert the wire i...

Страница 5: ...enters the resident s directory code on the controller keypad that resident s line is selected and rung The resident can talk with the visitor and allow entry at the main door or gate by dialing a 9 or at a second door or gate by dialling 5 2 Call waiting If the resident s telephone is in use two short tones will signal the visitor s call 3 If the resident dials a 2 the call in progress is put on ...

Страница 6: ...tes option Controlled doors or gates can be activated from the manager s or any off site tone dial telephone door gate control requires purchase of the remote programming option 8 Remote Programming option The Ovation system can be remotely programmed from the manager s or any outside tone dial telephone 9 Remote diagnostics option The Ovation system can be accessed via any terminal using a Hayes ...

Страница 7: ...connector board in the first LIB housing 2 Line Interface Boards LIBs Each LIB controls up to 12 resident telephone lines therefore a 55 unit building requires 5 LIBs Every 10 LIBs or part thereof are contained within an LIB housing located by the telephone junction box inside the building The LIBs are connected in a chain using 8 conductor flat telephone cables with an RJ45 connector on each end ...

Страница 8: ...tor flat telephone cables with an RJ45 connector on each end The first LIB in this stack is connected to the MUI WARNING The LIB housing is not weather proof and MUST be installed inside a building 3 Multiple Unit Interface Each controller is connected to the Multiple Unit Interface which can accommodate up to four controllers The MUI is connected to the first LIB in the LIB stack NOTE Only one co...

Страница 9: ...er Equivalence Number REN 0 1B Type of Connector Required USOC RJ71C 2 INSTALLING RJ71C JACKS Place the RJ71C jacks in series with incoming telephone lines so the Ovation can intercept the lines when a visitor wants to contact a resident Install the RJ71C jacks as follows 1 Each RJ71C jack handles 12 telephone lines so if you have a 55 unit building only 5 jacks will be needed If a unit has more t...

Страница 10: ...k installation and retain a copy for programming directory codes and directory making Copy this page for additional forms Sentex recommends using the LIB address as the jack number The installer should write the jack number on the front cover of each RJ71C jack Figure 4 LIB Planning Form ...

Страница 11: ...2500 feet in length NOTE Belden 8757 for unshielded installations and Belden 9504 for shielded installations or equivalent is recommended b A 2 conductor shielded cable from the Ovation Controller to the 120 VAC outlet for the 12 VAC 50 VA transformer supplied by Sentex or a 13 5 VDC power supply that you provide See Table 1 for the required wire size c A 2 conductor cable to the Ovation Controlle...

Страница 12: ...transformer supplied by Sentex or a 12 VDC power supply that you provide See Table 2 for the required wire size b A 4 twisted pair cable between the connector boards of each LIB housing in the stack as shown in Figure 6 applies only to installations with multiple LIB housings NOTE Belden 8757 for unshielded installations and Belden 9504 for shielded installations or equivalent is recommended Figur...

Страница 13: ...om each Ovation Controller to the 120 VAC outlets for the 12 VAC 50 VA transformers supplied by Sentex or a 13 5 VDC power supplies that you provide See Table 3 for the required wire size c 2 conductor cables from the Ovation Controller to the door strikes magnetic locks or gate operators for the 2 control relays on each controller d 2 conductor cables from the strike power supplies if required e ...

Страница 14: ...he connector boards of each LIB housing in the stack as shown in Figure 8 Refer to the figure for which pairs that need to be twisted for a multiple unit installation with multiple LIB housings diagram applies only to installations with multiple LIB housings NOTE Belden 8757 for unshielded installations and Belden 9504 for shielded installations or equivalent is recommended Figure 8 Multiple Entra...

Страница 15: ...ctor gently rock it from side to side while pulling on the cable 3 Remove the desired knock out 4 Mount the unit on the wall a Surface Mount Cabinets Install the two top screws bolts in the wall leaving them loose Hang the cabinet on the installed screws bolts Install the bottom screws bolts in the bottom openings Tighten all four screws bolts b Flush Mount Cabinets Cut hole in wall see Figure 9 f...

Страница 16: ...lace by its own grounding screw at the top of the housing 2 Mount the LIB housing s on the wall a Install the two top screws bolts in the wall leaving them loose b Hang the cabinet on the installed screws bolts c Install the bottom screws bolts in the bottom openings d Tighten all four screws bolts 3 Ground the housing to a suitable earth ground using the ground connection located on the upper rig...

Страница 17: ... installation Figure 11 LIB Types and Decade Switch Arrangements 1 SINGLE DECADE LIB SWITCH Single decade switch LIBs should be used only when there are 10 or less LIBs in your installation Set single decade switch LIB addresses as follows 1 Set LIB address numbers by working from right to left starting with the number 0 For a 10 LIB installation the decade switch on the the far right LIB will be ...

Страница 18: ...e fourth LIB from the right in the second LIB housing is 023 because 02 is the housing number and 3 is the LIB number Once the LIB addresses are set determining the address of individual lines is easy For example The third line on the the fourth LIB from the right in the second LIB housing is addressed 02303 because 02 is the housing number 3 is the LIB number and 03 is the line number The elevent...

Страница 19: ...connected to the negative side of the coil B LIB Control Single Unit Installations Plug the 4 twisted pair cable from the Ovation converter board into TB1 on the connector board in the first LIB housing Multiple Unit Installations Plug the 4 twisted pair cable from the Ovation converter board into TB1on the MUI in the first LIB housing Plug the four twisted pair cables from additional Ovation cont...

Страница 20: ...Rev B Doc 6001072 Page 19 of 28 Figure 12 Ovation Controller Board Connections Adjustments and Indicators ...

Страница 21: ...ecial ordered from Sentex 3 Repeat steps 1 and 2 for each RJ71C and associated LIB IMPORTANT NOTE If any residents have 3 way calling either their 3 way calling service or the optional Ovation call waiting feature must be discontinued Otherwise when call waiting is activated the Ovation will trigger the 3 way calling feature and the tenant will be connected to a dial tone To discontinue call waiti...

Страница 22: ...Rev B Doc 6001072 Page 21 of 28 Figure 14 LIB Connections and Indicators ...

Страница 23: ... short 8 conductor cables with RJ45 connectors provided with the LIBs Connect them from J1 OUT of one LIB to J2 IN of the next LIB 3 Repeat step 2 until all LIBs in the housing are connected 4 For Multiple LIB Housings connect a 4 twisted pair cable from TB5 on the MUI in the first housing to TB1 on the MUI in the next housing 5 Continue until all LIB housings are connected After you have finished...

Страница 24: ...e Ovation to provide access Devices wired to ST1 and COM on TB1 activate Relay 1 Devices wired to ST3 and COM on TB2 activate Relay 2 if Relay 2 is set as a control Use shielded cable such as Belden 8771 with the shield connected to the Controller board ground screw When contact closure occurs the system activates the associated relay for the programmed period of time 3 DOOR POSITION SENSING The O...

Страница 25: ...3 Enter programming step 69 followed by the three digit LIB number the two digit line number of the line you wish to use for this test and the key When you hear the tone adjust the SIDETONE BALANCE pot on the Ovation controller board to minimize the DC voltage between these two points 3 VERIFYING TELEPHONE AND DOOR GATE CONNECTIONS 1 Incoming Line Test To verify system connections each resident s ...

Страница 26: ...on their telephone 2 Verify the device attached to relay 1 activates for the specified period of time and that 10 beeps are emitted from the front panel speaker 3 If there is a second door or gate connected to relay 2 call a resident from the keypad located at the front entrance to the building complex When the resident answers their telephone identify who you are and ask them to press a 5 on thei...

Страница 27: ...ime C O BUSY DS6 This indicator lights when the controller calls an outside telephone number i e not a resident RINGING HOME DS7 This indicator flashes when the controller is ringing a resident POWER ON DS9 This indicator lights if power is connected to the system RELAY 2 ACTIVE DS10 This indicator remains lit while Relay 2 is activated for the programmed time 2 LINE INTERFACE BOARD LIB Line Inter...

Страница 28: ...ines as it may cause harm to the network If the telephone company notes a problem they may temporarily discontinue service When practical they will notify you in advance of the discontinuation If advance notice is not feasible you will be notified as soon as possible When you are notified you will be given the opportunity to correct the problem and informed of your right to file complaint with the...

Страница 29: ...ified equipment should be made by an authorized Canadian maintenance facility designated by the supplier Any repairs or alterations made by the user to this equipment or equipment malfunctions may give the telecommunications company cause to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephon...

Отзывы: