Rev B
Doc. 6001072
Page 11 of 28
DC POWER
WIRE SIZE
DISTANCE
AC POWER
WIRE SIZE
18 AWG
30' and under
18 AWG
18 AWG
30'-75'
14 AWG
14 AWG
75'-150'
12 AWG
12 AWG
150'-250'
10 AWG
10 AWG
250'-500'
-----
Table 1. Single Entrance Ovation Cabling Power Wire Distance.
B. Line Interface Board Cabling
The following cabling must be run for a single entrance installation:
a. A 2 conductor shielded cable
from the LIB to the 120 VAC outlet for the 12 VAC, 50 VA
transformer supplied by Sentex (or a 12 VDC power supply that you provide). See Table 2 for
the required wire size.
b. A 4 twisted pair cable
between the connector boards of each LIB housing in the stack, as
shown in Figure 6 (applies only to installations with multiple LIB housings).
NOTE:
Belden 8757 for unshielded installations and Belden 9504 for shielded installations (or
equivalent) is recommended.
Figure 6. Single Entrance LIB Cabling.
DC POWER
WIRE SIZE
DISTANCE
AC POWER
WIRE SIZE
18 AWG
30' and under
16 AWG
18 AWG
30'-75'
12 AWG
14 AWG
75'-150'
10 AWG
12 AWG
150'-250'
-----
10 AWG
250'-500'
-----
Table 2. Single Entrance LIB Cabling Power Wire Distance.