www.sentera.eu
MIW-FCVC8-R-EN-000 - 28 / 08 / 2019
8 - 12
ATTENTION
Do not expose to direct sunlight!
NOTE
The sensor is not designed, manufactured or intended for control or monitoring
equipment in environments requiring life safety performance, in which the failure
of the sensor could lead directly to death, personal injury, or severe physical or
environmental damage.
OPERATING INSTRUCTIONS
The unit is supplied with electrical energy at voltages high enough to inflict personal
injury or threat to health.
ATTENTION
NOTE
The compounds released from plastics may influence the sensor readings. Please
allow several days for the sensor to stabilize before you obtain the accurate
values.
Calibration procedure:
Sensor calibration is not necessary. All sensor elements are calibrated and tested in
our factory.
In the unlikely event of TVOC / CO
2
eq sensor element failure, this component can be
replaced.
Bootloader
Thanks to the bootloader functionality, the sensor firmware can be updated via
Modbus RTU communication. To enter ‘Boot mode”, put a jumper onto pins 3 and
4 of the P1 header and restart the power supply (see
Fig. 6
). Once ‘Boot mode’ is
activated, the firmware can be updated via SM Boot application (part of 3SModbus
software suite) or Sensistant.
Fig. 6 P1 header
1 2 3 4 5
Put a jumper onto pins 1 and 2 and wait
for at least 5 seconds to reset the Modbus
communication parameters
1 2 3 4 5
Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode
LED indications
1.
When the green LED is on, the measured value (temperature, relative humidity
or TVOC / CO
2
eq) is between the minimum and maximum alert range values (
Fig.
7 - 1
).
2.
When the yellow LED is on, the measured value (temperature, relative humidity
or TVOC / CO
2
eq) is in the alert range (
Fig. 7 - 2
).
3.
When the red LED is on, the measured value (temperature, relative humidity or
TVOC / CO
2
eq) is below the minimum measurement range value or above the
maximum value. Blinking red LED indicates loss of communication with a sensor
(
Fig. 7 - 3
).
FCVC8-R
INTELLIGENT MULTIFUNCTIONAL
FLUSH MOUNTED SENSOR