www.sentera.eu
MIW-STVS1-EN-000 - 24 / 03 / 2022
5 - 9
STVS1
230 VAC TRANSFORMER CONTROLLER WITH
ANALOGUE INPUT
OPERATIONAL DIAGRAM
L22 series
Analogue input /
Control signal
U (VAC)/
Speed
0
4
6
8
9,5
110
0
140
170
190
230
2
Switching levels
Up
2; 4; 6; 8; 9,5 VDC
Down
Up level — 0,2 VDC
WIRING AND CONNECTIONS
Wiring and connections
L
Power supply, phase (230 VAC / 50—60 Hz)
N
Power supply, neutral
Pe
Earth terminal
Pe
Earth terminal
L1
Unregulated output, line
N1
Unregulated output, neutral
N1
Regulated output to motor, neutral
U
Regulated output to motor, line
TK
Input - TK monitoring for thermal motor protection
TK
0V
Ground
+12V
Output 12 VDC / Imax 50 mA
+V*
Digital output 12 VDC / Imax 50 mA (0 VDC = TK fault; 12 VDC =
normal operation)
V/C
Input U: 0—10 VDC
ATTENTION
The total output current for both outputs (+12V and +V) must not exceed
100 mA!