background image

www.sentera.eu

MIW-STVS1-EN-000 - 24 / 03 / 2022

4 - 9

back to the table of contents

STVS1

230 VAC TRANSFORMER CONTROLLER WITH
ANALOGUE INPUT

PRODUCT DESCRIPTION

The STVS1 series of transformer fan speed controllers regulate the speed of 
single-phase voltage controllable motors in five steps by varying the output 
voltage according to an 0—10 VDC analogue input signal. They are equipped with 
autotransformer(s) and feature TK monitoring for thermal motor protection. The 
controllers up to 7,5 A are available in plastic enclosure, while the models above 7,5 
A are available in a metal enclosure. 

ARTICLE CODES

Article code

Rated max. current [A]

Fuse [A]

STVS1-15L22

1,5

(5*20 mm) T-2,5 A-H

STVS1-25L22

2,5

(5*20 mm) T-4,0 A-H

STVS1-35L22

3,5

(5*20 mm) T-5,0 A-H

STVS1-50L22

5,0

(5*20 mm) T-8,0 A-H

STVS1-75L22

7,5

(6*32 mm) T-12,5 A-H

STVS1100L22

10,0

(6*32 mm) T-16,0 A-H

STVS1130L22

13,0

(6*32 mm) T-20,0 A-H

INTENDED AREA OF USE

 

 Fan speed control of voltage controllable motors (pumps and fans) in ventilation 
systems 

 

For indoor use only

TECHNICAL DATA

 

 Supply voltage: 230 VAC / 50—60 Hz

 

Maximum motor current (Imax): 13 A

 

Unregulated output: 230 VAC (Imax. 2 A)

 

TK monitoring for thermal motor protection

 

12 VDC to supply an external device (e.g. potentiometer)

 

 5 switching levels according to the input signal

 

LED status indication

 

 Enclosure: plastic (R-ABS, UL94-V0, grey RAL 7035) or sheet steel (RAL 7035, 
polyester powder coating), depending on the product version 

 

Protection standard: IP54 (according to EN 60529)

 

Operating ambient conditions:

 

Temperature: -20—35 °C

 

Rel. humidity: 5—95 % rH (non-condensing)

STANDARDS

 

Low Voltage Directive 2014/35/EC 

 

EMC Directive 2014/30/EC: EN 61326

 

WEEE Directive 2012/19/EC

 

RoHs Directive 2011/65/EC

Содержание STVS1 Series

Страница 1: ...STVS1 230 VAC TRANSFORMER CONTROLLER WITH ANALOGUE INPUT Mounting and operating instructions ...

Страница 2: ...ALOGUE INPUT Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 8 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 ...

Страница 3: ...fect the product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts A...

Страница 4: ...STVS1 50L22 5 0 5 20 mm T 8 0 A H STVS1 75L22 7 5 6 32 mm T 12 5 A H STVS1100L22 10 0 6 32 mm T 16 0 A H STVS1130L22 13 0 6 32 mm T 20 0 A H INTENDED AREA OF USE Fan speed control of voltage controllable motors pumps and fans in ventilation systems For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current Imax 13 A Unregulated output 230 VAC Imax 2 A TK monitoring fo...

Страница 5: ...NS Wiring and connections L Power supply phase 230 VAC 50 60 Hz N Power supply neutral Pe Earth terminal Pe Earth terminal L1 Unregulated output line N1 Unregulated output neutral N1 Regulated output to motor neutral U Regulated output to motor line TK Input TK monitoring for thermal motor protection TK 0V Ground 12V Output 12 VDC Imax 50 mA V Digital output 12 VDC Imax 50 mA 0 VDC TK fault 12 VDC...

Страница 6: ...vice will get For example in a technical room the correct installation height can be of great importance 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any responsibilities For metal enclosures above 7 5 A 4 Once secured in position the mounting scr...

Страница 7: ...P P P P P P P P P P P P P P P P P P P P P P P X1 X1 X1 X1 X1 X1 X1 X1 X1 1 1 1 1 X1 X1 1 X1 1 1 1 X1 1 1 1 1 1 1 X X X X X X X1 1 X1 X X X X1 X1 1 X1 X1 X1 X1 X1 1 1 X10 0K 0 0 0K 0K 0 0K 0K 0 0 0K K K K K K K K K K K K K 0K K 0K 0K 0 0 0 0K K K K K K K K K K 0K K K 0K 0K 0 0 0 0 0K K K K K K K K K 0K 0 0 0 0 0 0 0K K K K K K K K K 0 0 0 0 0 0 0K K K K K K 0K K K K 0K 0 0 0 0 0 0 0 0 0K K K K 0K 0...

Страница 8: ...ON ATTENTION Use only tools and equipment with non conducting handles when working on electrical devices After connecting the unit to the mains supply the green LED on its cover should light up to indicate that the controller is supplied Safe operation depends on proper installation Before start up ensure the following The mains supply is connected correctly Protection is provided against electric...

Страница 9: ...alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should b...

Отзывы: