PRODUCT DESCRIPTION

The RMFPX-2R are multifunctional room controllers featuring 

 

adjustable temperature, relative humidity and CO

setpoints. They 

have a wide range of low voltage power supply. The control algorithm 
controls one single analog / modulating output based on the measured 
T, rH and CO

2

 values. All parameters are accessible via Modbus RTU. 

ARTICLE CODES

Code

Supply 

Connection

RMFPG-2R

18—34 VDC / 15—24 VAC ±10 %

3-wire

RMFPF-2R

18—34 VDC

4-wire

INTENDED AREA OF USE

 

 Control of indoor temperature, relative humidity and CO

level in HVAC applications

 

Suitable for residential and commercial buildings

 

For indoor use only

TECHNICAL DATA

 

Fan speed control based on T, rH and CO

2

 

 

Analog / modulating output type: 

 

0—10 VDC mode: min. load 50 kΩ (R

L

 ≥ 50 kΩ) 

 

0—20 mA: max. load 500 Ω (R

L

 ≤ 500 Ω) 

 

 PWM (open-collector type): PWM Frequency: 1 kHz, min. load 50 kΩ (R

L

 ≥ 50 kΩ); 

PWM voltage level 3,3 or 12 VDC

 

Selectable temperature range: 0—50 °C

 

Selectable relative humidity range: 5—85 %

 

Selectable CO

2

 range: 0—2.000 ppm 

 

Removable sensor CO

element for easy calibration and verification

 

Compatible with SSCDM - Sentera Sensor Calibration Device

 

3 LEDs for status indication

 

 Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (5—85 % rH); ±30 ppm CO

2

  (0—2.000 ppm 

CO

2

), depending on the selected parameter

 

Enclosure:

 

rear plate: plastic ABS, black (RAL 9004)

 

front cover: ASA, ivory (RAL 9010)

 

Protection standard: IP30 (according to EN 60529)

 

Operating ambient conditions: 

 

temperature: 0—50 °C

 

rel. humidity: 5—85 % rH, (non-condensing)

 

Storage temperature: -10—60 °C

STANDARDS 

 

Low Voltage Directive 2014/35/EC;  

 

 

 - EN 60529:1991 Degrees of protection provided by enclosures (IP Code) 
Amendment AC:1993 to EN 60529

 

 - EN 60730-1:2011 Automatic electrical controls for household and similar use - 
Part 1: General requirements

RMFPX-2R

MULTIFUNCTIONAL 
ROOM CONTROLLER

Содержание RMFPX-2R

Страница 1: ...Mounting and operating instructions RMFPX 2R MULTIFUNCTIONAL ROOM CONTROLLER ...

Страница 2: ...ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 MODBUS REGISTER MAPS 9 TRANSPORT AND STORAGE 11 WARRANTY AND RESTRICTIONS 11 MAINTENANCE 11 RMFPX 2R MULTIFUNCTIONAL ROOM CONTROLLER ...

Страница 3: ...ossible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is live Always disconnect the power suppl...

Страница 4: ...50 kΩ 0 20 mA max load 500 Ω RL 500 Ω PWM open collector type PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 5 85 Selectable CO2 range 0 2 000 ppm Removable sensor CO2 element for easy calibration and verification Compatible with SSCDM Sentera Sensor Calibration Device 3 LEDs for status indication A...

Страница 5: ...1 65 EC OPERATIONAL DIAGRAMS AO1 max range AO1 min range 60 40 100 0 rH Min range 0 5 0 CO2 Min range CO2 Max range Max Min T Min range T Max range rH Max range AO1 50 85 2 000 rH T C CO2 ppm Note The output changes automatically depending on the highest T rH or CO2 values i e the highest of three output values controls the output See the green line in the operational diagram above WIRING AND CONN...

Страница 6: ... 2 Insert the cables through the opening on the rear plate See Fig 2 Mounting dimensions 3 Using suitable fastening materials not supplied position the room sensor at least 1 5 m from the floor When planning the installation allow enough clearance for maintenance and service Mount the sensor in a well ventilated area Mind the correct mounting position and unit dimensions See Fig 2 and Fig 3 Fig 1 ...

Страница 7: ...T Master Slave n ATTENTION If an AC power supply is used with any of the units on a Modbus network the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT USB RS485 converter This may cause permanent damage to the communication semiconductors and or the computer ATTENTION Do not exceed the maximum power supply rating Measure before installation Unregulated 24 VAC sup...

Страница 8: ... at least 5 seconds to reset the Modbus communication parameters 1 2 3 4 5 Put a jumper onto pins 3 and 4 and restart the supply to enter bootloader mode LED indications 1 When the green LED is on the measured value temperature relative humidity or CO2 is between the minimum and maximum alert range values Fig 6 1 2 When the yellow LED is on the measured value temperature relative humidity or CO2 i...

Страница 9: ...1 when the measured value is outside the temperature alert values defined by holding registers 20 and 21 0 1 0 1 Measured temperature is OK Measured temperature is too high low 15 Relative humidity alert flag unsigned int Flag indicates that measured relative humidity is outside set alert values Set to 1 when the measured value is outside the relative humidity alert values defined by holding regis...

Страница 10: ... 0 ºC 22 Minimum relative humidity alert unsigned int Minimum relative humidity alarm value Min relative humidity range Max relative humidity alarm 50 200 20 0 rH 23 Maximum relative humidity alert unsigned int Maximum relative humidity alarm value Min relative humidity alarm Max relative humidity range 850 850 85 0 rH 24 Minimum CO2 alert unsigned int Minimum CO2 alarm value Min CO2 range Max CO2...

Страница 11: ...ublication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the supply Pay attention t...

Отзывы: