WIRING AND CONNECTIONS

RJ45 connection

/B

A

GND

24 VDC

8 mm

8 mm

8 mm

8 mm

RJ45

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

3

4

5

6

3

4

Pin 1

Supply voltage, 24 VDC   

Pin 2
Pin 3

Modbus RTU communication, signal A

Pin 4
Pin 5

Modbus RTU communication, signal /B

Pin 6
Pin 7

Ground, supply voltage

Pin 8

ATTENTION

Make sure that supply voltages from different power sources do not come into 
contact with each other. Never connect cables in the MDB-M-6 with Power wires 
(pins 1,2,7 and 8), connected to different Power supplies. If the connected units 
have a different Power supply, only crimp the data wires (pins 3,4,5,6) in the RJ45 
connectors. (See “Wiring and Connections”).

MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the unit, read carefully 

Safety and Precautions”

. Choose 

a smooth surface for installation: a wall, panel, etc.

Follow these steps:

1. 

Unscrew the front cover of the enclosure to remove it.

2. 

 Fix the enclosure onto the surface by means of suitable fasteners while adhering 
to the mounting dimensions in 

Fig. 1

 

Mounting dimensions 

and the correct 

mounting position in 

Fig. 2

 

Mounting position

.

Fig. 1 Mounting dimensions

Fig. 2 Mounting position

82

143,3

MDB

31

Correct

Incorrect

MDB

MDB

MDB

3. 

Insert the cables though the cable glands.

4. 

Crimp the RJ45 cable.

POWER OVER MODBUS 
DISTRIBUTION BOX

MDB-M-6

Содержание MDB-M-6

Страница 1: ...Mounting and operating instructions MDB M 6 POWER OVER MODBUS DISTRIBUTION BOX ...

Страница 2: ...CAUTIONS 3 PRODUCT DESCRIPTION 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 WIRING AND CONNECTIONS 4 MOUNTING INSTRUCTIONS IN STEPS 5 VERIFICATION OF INSTALLATION 6 TRANSPORT AND STORAGE 6 WARRANTY AND RESTRICTIONS 6 MAINTENANCE 6 POWER OVER MODBUS DISTRIBUTION BOX MDB M 6 ...

Страница 3: ...nvironment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecti...

Страница 4: ...ng ambient conditions temperature range 30 70 C rel humidity 20 90 rH non condensing STANDARDS Low Voltage Directive 2014 35 EU EN 60664 1 2007 Insulation coordination for equipment within low voltage systems Part 1 Principles requirements and tests EMC Directive 2014 30 EU EN 55022 2010 Information technology equipment Radio disturbance characteristics Limits and methods of measurement Amendment ...

Страница 5: ...f the connected units have a different Power supply only crimp the data wires pins 3 4 5 6 in the RJ45 connectors See Wiring and Connections MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the unit read carefully Safety and Precautions Choose a smooth surface for installation a wall panel etc Follow these steps 1 Unscrew the front cover of the enclosure to remove it 2 Fix the enclosure on...

Страница 6: ...s 1 2 7 and 8 connected to different Power supplies If the connected units have a different Power supply only crimp the data wires pins 3 4 5 6 in the RJ45 connectors See Wiring and Connections VERIFICATION OF INSTALLATION When the green LED on the left of each RJ45 socket is on supply voltage is detected see Fig 4 below Fig 4 Power indication ATTENTION The maximum power supply per channel must no...

Страница 7: ...e the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions these controllers are maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the main supply Pay attention that no...

Отзывы: