www.sentera.eu
MIW-MCS-1-LCD-EN-000 - 20 / 07 / 2016
8 - 33
RELAY CONTACT FUNCTION ACTIVE STATE COM - > NO
Tix/Aix,
[x]
COM
NO
Rcx,
[state]
COM
NC
SP-
Hysteresis
SP
TIX/AIX function
Active state
event
Inactive state
event
t,[s]
Rcx,
[state]
COM
NO
COM
NC
DIX function
RELAY CONTACT FUNCTION ACTIVE STATE COM -> NC
Tix/Aix,
[x]
COM
NO
Rcx,
[state]
COM
NC
SP-
Hysteresis
SP
TIX/AIX function
t,[s]
Active state
event
Inactive state
event
Rcx,
[state]
COM
NO
COM
NC
DIX function
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting your controller read carefully “
”. Choose a smooth surface for an installation location (a wall,
panel and etc.). Then proceed with the following mounting steps:
1
Switch off the power supply.
2
Unscrew the four screws on the front cover and open it carefully.
ATTENTION
Make sure the flat cable, connecting the motherboard with the LCD printed circuit
board remains in place!
3
Insert the connecting cables through the cable glands of the unit.
4
Do the wiring according to the wiring diagram (see
Fig 1
) using the information
from section “
Wiring and connections
”. Connect the controlled equipment and
the sensors (if necessary). Use cables with recommended length and type with
respect to your application. Mind the following recommendations:
►
Use shielded cables for the analogue inputs / outputs in case the cable length
is between 4 and 12 m and voltage (VDC) mode is used.
►
When the cable length exceeds 12 m, use the analogue inputs / outputs in
current (mA) mode.
Fig 1 Wiring and connections
Power supply
Line
Neutral
Relay contact 1
Normally closed
Common
Normally open
Relay contact 2
Normally open
Common
Normally closed
PT 500 / PT1000
PT 500 / PT1000
Analogue inputs
Digital inputs
Analogue outputs
Supply
output
Modbus
RTU
ATTENTION
When you first use the unit make sure that the load corresponds to the default
output values. If the default values do not fit the load used, configure the unit
first, then connect the load. Improper load may cause damage to the controller.