PARAMETERS AND DEFAULT SETTINGS
GENERAL
Parameter
Default value
Temperature input 1 and 2 (
T1
&
T2
)
Input state
In use
Sensor range
-30—70 °C
Control range
0—40 °C
Off level
-10 °C
Setpoint
20 °C
Hysteresis
2 °C
Units
Celsius
Calibration
Stand-by
Analogue input 1 and 2 (
Ai1
&
Ai2
)
Input type
Not in use
Sensor range
0—10,0 VDC
Measured quantity
Relative humidity
Reference sensor range
20—80 % rH
Control range
20—80 % rH
Off level
20 % rH
Setpoint
50 % rH
Hysteresis
6 % rH
Free units
Empty
Digital input 1, 2, 3 and 4 (
Di1
,
Di2
,
Di3
&
Di4
) Function
Not in use
Active state
Low
Analogue output 1 and 2 (
Ao1
&
Ao2
)
Output type
0—10,0 VDC
Output function
Linear
Output mode
Cool
Minimum value
0 %
Maximum value
100 %
Time to maximum
60 s
Kp value
1,0 gain
Ti value
10 s
Td value
1 s
Autotune PID control
Stand-by
Analogue output 1 (
Ao1
)
Assigned normal input
Temperature input 1 (T1)
Assigned high priority input
Analogue input 2 (Ai2)
Analogue output 2 (
Ao2
)
Assigned normal input
Temperature input 2 (T2)
Assigned high priority input
Analogue input 1 (Ai1)
Analogue output relation
Free
Unbalance coefficient
0 %
Relay contacts 1 and 2 (
Rc1
&
Rc2
)
Assigned input(s)
Not in use
Functionality
Device functionality
Temperature Cool
Passwords
Installer password
0000
User password
0000
MCS-1-LCD
MULTIFUNCTIONAL LOGIC
CONTROLLER