MIW-EVSS-DM-EN-000 - 18 / 12 / 2018
11 - 16
ATTENTION
The status of the LEDs can be checked only when the unit is energised. Take the
relevant safety measures!
OPERATING INSTRUCTIONS
OPERATION MODES
In Modbus mode
you control the parameters: Umax, Umin, Kick start / Soft start,
Off level enable / disable and Off level value through Modbus registers.
In Standalone mode
you control the parameters: Umax, Umin, Kick start / Soft start,
Off level enable / disable and Off level value by means of the hardware settings (DIP
switch, trimmers, jumpers).
In Normal mode
if Off level is disabled, Softstart / Kickstart is executed only once -
after the controller is supplied; otherwise Softstart / Kickstart is executed every
time the controller is switched on.
When
Timer mode
is selected, the controller receives a pulse control signal from the
remote control switch. When Logic mode is selected, the controller receives a pulse
control signal from the Ai input.
In both modes
Timer mode
and
Logic mode
the pulse width is to be more than 30
ms; otherwise the signal is filtered.
FRONT PANEL LED INDICATION
When the green LED on the front cover (
Fig. 10
) gives out a continuous light, the
controller operates in normal mode. When it blinks:
►
the controller operates in remote control mode, or
►
OFF level is enabled and the analog input signal is below the OFF level value.
The red LED on the front cover (
Fig. 10
) indicates overheating of the motor. When
it is on, the controller stops the motor. To restart operation after eliminating the
cause for overheating, disconnect the unit from the mains supply for a few seconds
and then connect it again.
Fig. 10 Operation indication
EVSS
ELECTRONIC FAN SPEED
CONTROLLER WITH TK