www.sentera.eu
MIW-DXH-EN-001 - 02 / 10 / 2017
5 - 10
OPERATIONAL DIAGRAMS
Analogue
output
[VDC]
min.
range
max.
range
10
0
100
rH, [%]
Relay
output
rel on
0
100
rH, [%]
rel off
SP-hyst SP
WIRING AND CONNECTIONS
Vin
Positive DC voltage / AC ~
GND
Ground / AC ~
A
Modbus RTU (RS485) signal A
/B
Modbus RTU (RS485) signal /B
Ao1
Analogue output (0—10 VDC / 0—20 mA)
GND
Ground
NO1
Normally open contact
COM1
Common contact
NC1
Normally closed contact
Connections
Cable cross section: max. 1,5 mm
2
Cable gland clamping range: 5—10 mm
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the DXH sensor / switch read carefully
“Safety and
Precautions”
. Then proceed with the following mounting steps:
1.
Open the cover and insert the connecting cables through the cable gland of
the unit.
2.
Do the wiring according to the wiring diagram (see
Fig. 1
) using the information
from section “
Wiring and connections
”.
Fig. 1 Wiring diagram
Analogue output
0
—10 VDC / 0—20 mA
Relay 1 contacts
Normally open
Common
Normally closed
Modbus RTU
/B A
Power supply
13
—26 VAC / 18—34 VDC
DXH
DUCT HUMIDITY
SENSOR / SWITCH