HOLDING REGISTERS
Holding Registers
Data type
Description
Data
Values
20
Maximum relative humidity
range
unsigned int
Maximum value of relative humidity range,
cannot be set less than minimum relative
humidity range plus 5%
Min+50—1.000
default: 1.000
850 = 85 % rH
21
Minimum relative humidity
alert
unsigned int
Minimum relative humidity alarm value
Min. relative humidity range—Max.
relative humidity alarm
default: 0
200 = 20,0 % rH
22
Maximum relative humidity
alert
unsigned int
Maximum relative humidity alarm value
Min. relative humidity alarm —Max.
relative humidity range
default: 1.000
850 = 85 % rH
23
Minimum CO
2
range
unsigned int
Minimum CO
2
range, cannot be set higher than
maximum CO
2
range minus 100 ppm
0—Max-100
default: 400
1.000 = 1.000 ppm
24
Maximum CO
2
range
unsigned int
Maximum CO
2
range, cannot be set less than
minimum CO
2
range plus 100 ppm
Min+100—2.000
default: 2.000
2.000 = 2.000 ppm
25
Minimum CO
2
alert
unsigned int
Minimum CO
2
alarm value
Min. CO
2
range—Max. CO
2
alarm
default: 400
400 = 400 ppm
26
Maximum CO
2
alert
unsigned int
Maximum CO
2
alarm value
Min. CO
2
alarm —Max. CO
2
range
default: 2.000
2.000 = 2.000 ppm
27—39
Reserved, return 0
40
CO
2
module self calibration
unsigned int
Enables or disables the CO
2
module self
calibration technique. If enabled it is advisable
that the CO
2
concentration drops to outside
level (400 ppm) in a 7 day period.
0—1
default: 1
0 = Disabled
1 = Enabled
41
Output 1 type (T)
unsigned int
Select analogue / modulating output 1 type
1—3
default: 1
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
42
Output 1 overwrite (T)
unsigned int
Enables the direct control over the temperature
output.
0—1
default: 0
0 = Disabled
1 = Enabled
43
Output 1 overwrite value (T)
unsigned int
Overwrite value for output 1. Active only if
Holding register 42 is set to 1.
0—1.000
default: 0
0 = 0 %
1.000 = 100 %
44
Internal voltage source
selection Output 1 (T)
unsigned int
Selection of internal voltage source for PWM
output 1.
0—1
default: 0
0 = 3,3 VDC
1 = 12 VDC
45—50
Reserved, return 0
51
Output 2 type (rH)
unsigned int
Select analogue / modulating output 2 type.
1—3
default: 1
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
52
Output 2 overwrite (rH)
unsigned int
Enables the direct control over the relative
humidity output.
0—1
default: 0
0 = Disabled
1 = Enabled
53
Output 2 overwrite value
(rH)
unsigned int
Overwrite value for output 2. Active only if
Holding register 52 is set to 1.
0—1.000
default: 0
0 = 0 %
1.000 = 100 %
54
Internal voltage source
selection Output 2 (rH)
unsigned int
Selection of internal voltage source for PWM
output 2.
0—1
default: 0
0 = 3,3 VDC
1 = 12 VDC
55—60
Reserved, return 0
61
Output 3 type (CO
2
)
unsigned int
Select analogue / modulating output 3 type.
1—3
default: 1
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
62
Output 3 overwrite (CO
2
)
unsigned int
Enables the direct control over the CO2 output. 0—1
default: 0
0 = Disabled
1 = Enabled
63
Output 3 overwrite value
(CO
2
)
unsigned int
Overwrite value for output 3. Active only if
Holding register 62 is set to 1.
0—1.000
default: 0
0 = 0 %
1.000 = 100 %
64
Internal voltage source
selection Output 3 (CO
2
)
unsigned int
Selection of internal voltage source for PWM
output 3.
0—1
default: 0
0 = 3,3 VDC
1 = 12 VDC
65—80
Reserved, return 0
If you want to find out more about Modbus over serial line, please visit:
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
VERIFICATION OF INSTALLATION INSTRUCTIONS
If your unit does not function as expected, please check the connections.
DSMFX-2R