VERIFICATION OF INSTALLATION 

After switching on the power supply, the green ON/OFF LED on the printed circuit 
board must be on solid indicating that the unit is powered (

Fig.  12 

Operating 

indication

). If the LED is OFF, check the connections.

Blinking green RX and TX LEDs indicate that the unit has detected a Modbus 
network (

Fig. 13

). If they do not blink, check the connections.

Fig. 12 Operating indication

Fig. 13 Modbus communication 

indication

ON/OFF LED

TX - transmitting 

RX - receiving

The status of the LEDs can be checked only when the unit is powered. Take the 
relevant safety measures! 

ATTENTION

TRANSPORT AND STORAGE 

Avoid shocks and extreme conditions; stock in original packing.

WARRANTY AND RESTRICTIONS

Two years from the delivery date against defects in manufacturing. Any modifications 
or alterations to the product after the date of publication relieve the manufacturer 
of any responsibilities. The manufacturer bears no responsibility for any misprints or 
mistakes in this data. 

MAINTENANCE 

In normal conditions this product is maintenance-free. If soiled, clean with a dry or 
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these 
circumstances the unit should be disconnected from the supply. Pay attention that 
no fluids enter the unit. Only reconnect it to the supply when it is completely dry.

DUAL DIFFERENTIAL PRESSURE 
TRANSMITTER  WITH DISPLAY

DPD

Содержание DPD-F-10K

Страница 1: ...Mounting and operating instructions DPD DUAL DIFFERENTIAL PRESSURE TRANSMITTER WITH DISPLAY ...

Страница 2: ... CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 6 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 9 VERIFICATION OF INSTALLATION 13 TRANSPORT AND STORAGE 13 WARRANTY AND RESTRICTIONS 13 MAINTENANCE 13 DUAL DIFFERENTIAL PRESSURE TRANSMITTER WITH DISPLAY DPD ...

Страница 3: ...environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connect...

Страница 4: ...K0 15 24VAC 10 3 4 W 2 5 W 230 mA 0 4 000 Pa DPD G 10K 0 10 000 Pa INTENDED AREA OF USE Differential pressure measurement in HVAC applications Volume flow measurement in HVAC applications Air velocity measurement by using an external PSET PTX 200 Pitot tube connection set in HVAC applications Differential pressure volume flow monitoring in clean rooms Clean air and non aggressive non combustible g...

Страница 5: ...H non condensing Storage temperature 20 70 C STANDARDS EMC Directive 2014 30 EC EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test configuration operational conditions and performance crite...

Страница 6: ...nd This means that the ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC voltage Doing so might cause permanent damage to the connected devices MOUNTING INSTRUCTIONS IN STEPS Before you start mounting t...

Страница 7: ...l area cm in Modbus holding register 63 for sensor module 1 or in holding register 83 for sensor module 2 If you use PSET QF or PSET PVC enter the K factor of the fan provided by the fan motor manufacturer in Modbus holding register 62 for sensor module 1 or in holding register 82 for sensor module 2 In case the K factor is not known volume flow is calculated from a duct cross sectional area holdi...

Страница 8: ...age selection When the internal pull up resistors JP1 for sensor module 1 and JP2 for sensor module 2 are connected the voltage source is set via Modbus holding register 54 for sensor module 1 and holding register 74 for sensor module 2 i e 3 3 VDC or 12 VDC See Fig 5 Pull up resistor jumpers Fig 5 Pull up resistor jumpers JP2 JP1 When JP1 and JP2 are disconnected the output type is Open collector...

Страница 9: ... For the complete Modbus register data refer to the product Modbus Register Map which is a separate document attached to the article code on the website and contains the registers list Products with earlier firmware versions may not be compatible with this list NOTE OPERATING INSTRUCTIONS NOTE For detailed information and settings refer to the product Modbus register map which is attached to the a...

Страница 10: ...he printed circuit board blinks two times and do not release the switch until LED3 blinks again three times 2 All Modbus registers except the communication related registers 1 9 are reset to their default values factory pre set During the Modbus reset procedure the display will indicate H see Fig 8 Fig 8 Sensor calibration and Modbus holding register reset tact switches and indication SW2 SW1 ATTE...

Страница 11: ...ple of displaying 100 m3 h is given in Fig 10 a below 2 2 Air volume flow rate above 10 000 m3 h is displayed divided by 1 000 An example of displaying 10 000 m3 h is given in Fig 10 b below Fig 10 Air volume flow and air velocity mode indications 10 a Air volume flow mode 0 9999 m3 h 10 b Air volume flow mode 10 000 m3 h 3 Air velocity display mode 3 1 Air velocity is displayed with a resolution ...

Страница 12: ...Air velocity Under the minimum range Sensor 1 Sensor 2 Above the maximum range Sensor 1 Sensor 2 Within the range Sensor 1 Sensor 2 The display changes its indication as follows 1 Channel 1 indication 3 seconds 2 Channel 1 measured pressure volume flow air velocity 6 seconds 3 Channel 2 indication 3 seconds 4 Channel 2 measured pressure volume flow air velocity 6 seconds 5 Return to indication 1 D...

Страница 13: ...ke the relevant safety measures ATTENTION TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any mispri...

Отзывы: