background image

FlexPI Product Guide

Page 9

Wall protection

To protect walls, FlexPI sensor cable is attached directly to the wall. The cable spacing depends 
on the required level of security, the building material, and the height of the wall. For areas where 
the cable may be subject to damage from vandalism or equipment, the cable can be installed 
inside metal conduit, which is attached to the protected surface. The type of cable fasteners used 
to attach the cable to the wall also depends on the building material. Cable spacing ranges from a 
maximum of 1.25 m (4 ft.) to a minimum of 30 cm (1 ft.) and the cable fasteners should be used 
every 30 cm (1 ft.).

Roof protection

Most roofing materials can be protected from inside the building (see 

Figure 7:

). For large 

industrial buildings, steel beams are frequently used to support the roof. If the beams are 1.8 m 
(6 ft.) apart or less, the cable can be attached to the roof beams. If the spacing between beams is 
greater than 1.8 m, attach the cable to the underside of the roof. For wooden trusses, which are 
typically 60 cm (2 ft.) apart, the cable should be attached to each truss. This will provide a multiple 
pass installation which is often necessary on a wooden surface. Proper calibration is critical for 
roof installation to ensure adequate detection of a break-in attempt, while rejecting the noise and 
vibration caused by heavy rain.

Floor protection

To protect a floor, you must have access to the underside of the floor. Depending on the type of 
flooring, you can either attach the sensor cable to the support structure, or to the floor. As with 
other parts of the building, the type of building material dictates the number of cable passes 
required.

Embedding sensor cable

With careful planning, the sensor cable can be embedded in walls, floors, or even roofs during 
construction. The recommended method is to install metal conduit inside the structure during the 
construction phase. When the construction is complete, the sensor cable can be pulled through 
the conduit. Using conduit for this type of installation allows the cable to be replaced or repaired if 
there is cable damage, or a cable fault. Avoid any sharp bends in the conduit. Before installing the 
conduit, remove any burrs or sharp edges that were created when the sections were cut.

Windows and skylights

Windows and skylights can create a vulnerability for intrusion attempts. The recommended 
method for window/skylight protection is to install a security grille over the opening, and run sensor 
cable completely around and in close proximity to the opening (see 

Figure 6:

). In addition, other 

technologies such as glass breakage detectors and magnetic contacts can be used to increase the 
level of security for windows and skylights.

Pipes and data cables

The FlexPI system can be used to protect pipes and data cables (see 

Figure 8:

 and 

Figure 9:

). To 

protect a pipe, the Flex sensor cable is attached directly to the pipe, typically in a spiral pattern 
around the outside of the pipe. Any attempt to drill, cut, or otherwise damage the pipe will trigger 
an alarm. Data cables that carry sensitive information are generally installed inside conduit. The 
addition of a FlexPI cable to the conduit will provide protection against the penetration of the 
conduit in an attempt to access the data cable. 

Содержание FlexPI C8DA0402-001

Страница 1: ...Product Guide FlexPI Interior Intrusion Detection Sensor C8DA0402 001 Rev B January 13 2014 ...

Страница 2: ...dance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause ha...

Страница 3: ...s 10 2 Installation 15 Installing the sensor cable 15 Cable handling 15 Installing cable on security cages 16 Installing cable on walls 16 Installing cable on roofs 17 Installing cable on floors 17 Embedding sensor cable in buildings and walls 17 Protecting windows and skylights 17 Protecting pipes and data cables 17 Installing terminators 18 Splicing cable 19 Outdoor cable installation 19 Install...

Страница 4: ...ng the Threshold 32 Setting the cut Count and time Window 33 The Cut Profile 33 Setting the Climb Alarm parameters sustained attack 33 Setting the climb Time and Window 34 Area Preparation 35 Bar graph received signal strength indicator 35 Step 1 Setting the Filter Response 36 Step 2 Calibrating the FlexPI Gain Threshold 36 Setting the Climb Alarm parameters sustained attack 38 Setting the Cut Ala...

Страница 5: ...eter most intruders while alerting police or security Each FlexPI system is a self contained intrusion detection sensor consisting of a processor an enclosure up to 600 m of sensor cable and a terminator The cable mounting hardware power supply alarm communication wiring and alarm annunciator are Customer supplied Figure 1 FlexPI system components 300 m sensor cable 30 m lead in cable data cable p...

Страница 6: ...se bands that optimize the sensor s response for the protected surface and the expected type of attack Other detection parameters include the Climb Alarm Settings sustained attack the Cut Alarm Settings number of impacts Time Window time in which a sustained attack or the number of impacts must occur to generate an alarm Gain Settings four discrete signal amplification levels FlexPI also includes ...

Страница 7: ...ermine the security requirements and expectations for a FlexPI installation There are a number of factors which must be considered when planning the installation The primary factors are the value of the assets being protected and the required level of security For a high security application where a sophisticated attack is possible the sensor cable spacing should be kept at a minimum This will inc...

Страница 8: ...cm 1 ft Keep roofs separate from other parts of the installation For roof installation on steel beams the maximum recommended cable spacing is 1 8 m 6 ft On roofs with wooden trusses the cable spacing should match the spacing of the trusses typically 61 cm 2 ft Sensor cable can be installed directly on the underside of a roof s surface For increased security use additional cable passes on the lowe...

Страница 9: ...structure or to the floor As with other parts of the building the type of building material dictates the number of cable passes required Embedding sensor cable With careful planning the sensor cable can be embedded in walls floors or even roofs during construction The recommended method is to install metal conduit inside the structure during the construction phase When the construction is complete...

Страница 10: ...e to the mounting surface must hold the cable firmly against the surface without pressing into the jacket or damaging the cable The fasteners must be appropriate for the specific type of surface Figure 2 Double pass security cage installation use cable loops at support posts for increased sensitivity double cable pass using 1 m spacing on 3 m security cage 30 cm 12 in recommended cable tie spacing...

Страница 11: ...w security application single pass on 8 ft wall 61 cm 2 ft 61 cm 2 ft 61 cm 2 ft 61 cm 2 ft 2 44 m 8 ft terminator FlexPI processor sensor cable power data cable 81 cm 2 7 ft 81 cm 2 7 ft 81 cm 2 7 ft 2 44 m 8 ft terminator FlexPI processor sensor cable power data cable 1 22 m 4 ft 1 22 m 4 ft 2 44 m 8 ft terminator FlexPI processor sensor cable power data cable ...

Страница 12: ...nduit terminator FlexPI processor sensor cable power data cables sensor cable around windows 1 2 2 m terminator FlexPI processor sensor cable 61 cm 2 ft 3 ft reduced cable spacing on lower portion of roof NOTE Cable installed indoors on 4 f t 91 cm the underside of the roof sensor cable cable tie 30 50 cm data cable conduit sensor cable metal conduit fastener 1 m 3 25 ft max sensor cable ...

Страница 13: ... cable with permanent tape cable tie 30 cm sensor cable 12 in support post sensor cable 30 cm 12 in cable ties do not allow the sensor cable to be pinched between the post and the cage If the cage is tightly secured to the post wrap the cable around the post as illustrated cable clip sensor cable 30 cm 12 in cable clip mounting surface fastener sensor cable permanent tape 30 cm sensor cable 12 in ...

Страница 14: ...Page 14 FlexPI Product Guide Figure 15 Using corner loops 10 15 cm inside corner outside corner 4 6 in corner loop fastener 10 15 cm 4 6 in corner loop ...

Страница 15: ...g is a list of cable handling Do s and Don ts Apply consistent light tension approximately 2 25 kg 5 lbs while mounting the sensor cable Install the sensor cable in metal conduit if the cable is being installed in an area where it may be prone to damage from vandalism equipment or materials see Figure 10 DO NOT use plastic conduit When using cable ties to attach the sensor cable to a security cage...

Страница 16: ... at the hinged side of the door Continue installing the cable on the security cage Figure 16 illustrates sensor cable installation on a security cage door Installing cable on walls The cable spacing depends on the type of building material and the required level of security The maximum recommended spacing for any type of wall surface is 1 25 m 4 ft The minimum recommended spacing is 30 cm 1 ft see...

Страница 17: ...y heavy rain Installing cable on floors Attach the cable to the underside of the floor either directly to the subfloor or to the support structure Base the number of cable passes required on the type of floor Embedding sensor cable in buildings and walls This type of installation requires the installation of metal conduit inside the walls during the construction of the building Senstar recommends ...

Страница 18: ...fully separate the strands of the exposed braided shield Tightly twist the strands into a single conductor and then carefully remove 6 mm 0 25 in of insulation from the center conductor DO NOT nick the center conductor Insert the twisted shield into one of the terminals on the terminal block and tighten the screw Insert the center conductor into the adjacent terminal and tighten the screw Insert t...

Страница 19: ...als and tighten the screws Insert the 2 center conductors into the 2 adjacent opposing terminals and tighten the screws Ensure that shield meets shield and center conductor meets center conductor Line up the terminal block with the center of the splice enclosure and apply 3 or 4 wraps of electrical tape at each of the 2 points where the cable will fit into the cable guide bars Align the 2 taped se...

Страница 20: ...away from the beginning of the zone by connecting lead in cable to the processor and splicing the lead in to the sensor cable There are two flanges on the enclosure that include 5 mm 0 375 in holes for mounting the enclosure on a flat stable surface Figure 20 illustrates the FlexPI processor features and Table 1 includes feature descriptions Figure 21 shows a mounted enclosure The mounting hardwar...

Страница 21: ...THRESHOLD switch Sets the input signal amplification before the signal is processed 4 settings from 1 low to 4 high 12 Enclosure cover mounting holes X4 4a GAIN THRESHOLD LEDs 4 LEDs correspond to 4 Gain settings LED ON switch ON 13 T4 SENSOR CABLE connection GND SHIELD connect twisted braided shield FLEX IN CENTER connect center conductor 5 S5 MISC switch miscellaneous controls S5 1 sets the freq...

Страница 22: ...Installing the processor Page 22 FlexPI Product Guide Figure 21 Enclosure mounting mounting hardware sensor cable alarm data cable and power cable ...

Страница 23: ...4 Sensor cable and lead in cable connections are made exactly the same way Figure 22 illustrates the sensor cable connection procedure Pass the sensor cable or lead in cable through the left side cable gland Prepare the cable for connection by following steps 1 2 and 3 in Figure 17 Figure 22 Connecting the sensor cable lead in cable 4 5 Insert the terminal block into T4 Insert the twisted shield a...

Страница 24: ...s are complete and verified Figure 23 shows the sensor cable to processor connection procedure Figure 24 shows the input output wiring connections to the FlexPI processor Figure 23 Connecting the data and power cables 2 3 1 Feed the data and power cable through the right Replace terminal block T5 and tighten the cable Carefully remove 6 mm 0 25 in of insulation side cable gland remove terminal blo...

Страница 25: ...ns sensor cable relay output and RELAY CONNECTIONS 30V 0 5 A RELAY T5 PWR INPUT 12 48 VDC T4 SUPERVISION SONALERT ALARM NC COM NO NC COM NO COM NO FLEX IN GND VDC VDC ALARM NO ALARM COM ALARM NC SONALERT NO SONALERT COM SUPERVISION NO SUPERVISION COM SUPERVISION NC SHIELD CENTER power input connections ...

Страница 26: ...Installing the processor Page 26 FlexPI Product Guide ...

Страница 27: ...ter Settings sets the sensor s frequency response Sensitivity Switch SW2 Gain Threshold Settings S4 Gain Settings Cable sets the amplification of the input signal received from the sensor cable before processing Impact Count Selector JP4 Cut S3 Cut Alarm Settings Window sec Threshold Count Cut Profile Sets the number and intensity of discrete impacts which must occur within the specified time Wind...

Страница 28: ...cted surface For example To simulate an impact attack Cut Alarm strike the surface using moderate to strong force with a hard object such as the handle or blade of a large screwdriver Wait approximately two seconds between impacts and wait about four seconds after each Cut Alarm to allow the processor s filters to clear To simulate a sustained attack Climb Alarm on a hard surface e g brick cinder ...

Страница 29: ...justments before changing the processor s settings First make the changes using the calibrate tool Then view a magnitude or frequency response plot using the new settings while testing the installation If the changes do not result in the required level of detection continue making and reviewing adjustments When the results are satisfactory download the new parameters to the processor CAUTION Some ...

Страница 30: ...ned activity is added to the total Time 10 Time Sets the period of Time that the received signal must exceed the climb Threshold to cause an alarm The Time must be accumulated within the climb alarm Window setting 2 sec Filter Settings The filter settings are used to customize the sensor s frequency response to the type of mounting surface and the installation environment Correct adjustment of the...

Страница 31: ...the length of the cable 6 Once the Frequency response is adequate close the Calibrate tool save the UCM file and download the new settings to the processor Step 2 Calibrating the Gain Settings The Cable Gain is used to amplify the input signal from the sensor cable before it is processed FlexPI has four Cable Gain Settings ranging from 1 lowest to 4 highest 1 Using the sensor s default Gain Settin...

Страница 32: ... surface 2 If any of the attack simulations impacts do not register as Cut Counts lower the Cut Alarm Threshold 3 Repeat this process until each simulated attack impact registers as a Cut Count and leads to an alarm 4 Once the Threshold is set monitor the system for nuisance alarms If the nuisance alarm rate NAR is unacceptable try to determine and correct the source Otherwise raise the Threshold ...

Страница 33: ...arm parameters sustained attack 1 Start recording a UCM Magnitude response plot tool and perform the simulated sustained attack scenario along the protected surface 2 If the attack simulation does not cause an alarm lower the Climb Alarm Threshold and repeat the tests 3 Repeat this process until the simulated attack always causes a Climb alarm 4 Once the Threshold is set monitor the system for nui...

Страница 34: ... also affect the Cut Alarm Settings If the Cut Alarm parameters have already been set retest and if required adjust the Cut Alarm parameters after changing the Cable Gain setting Note For settings available via the UCM that are not adjustable using the onboard switches the default values listed in the UCM apply Figure 26 Calibration switches S1 CLIMB S2 TIME WINDOW S3 CUT S4 GAIN THRESHOLD S5 MISC...

Страница 35: ...oring sawing cutting digging chiselling climbing If the Time Window lapses before the Time setting is exceeded the processor resets both parameters S2 Time Window Sets the maximum time in which the specified Climb Time must accumulate to cause an alarm AND Sets the maximum time in which the specified number of Cuts impacts must occur to cause an alarm 8 to 128 seconds S3 Cut Sets the number of imp...

Страница 36: ...length of the sensor cable Look for a response that is above the Threshold 6th LED is illuminated but below the top of the bar graph 10th LED is OFF 4 If the signal response does not illuminate the green LED increase the Gain setting one level and repeat the test OR If the signal response always reaches the top of the bar graph decrease the Gain setting one level and repeat the test 5 When the imp...

Страница 37: ...he switches conduct tests sensor alarms raise gain monitor NAR too many NAs calibration complete lower gain too many NAs sensor alarms change frequency response band reset gain to 2 and return to first conduct tests calibrate via UCM OR redeploy cable and repeat procedure conduct tests N Y Y N N Y Y N monitor NAR NAR nuisance alarm rate NAs nuisance alarms gain already at maximum N Y N Y both resp...

Страница 38: ...is 4 impacts and the Time Window is 32 seconds If the security regulations at your facility do not define specific Cut Count and Time Window settings then these parameters should be set according to the probability of nuisance impacts occurring within a specific timeframe For example if nuisance impacts can occur but never in rapid succession then the Cut Count can be set to 2 with a short Time Wi...

Страница 39: ...e is an advanced parameter which can be adjusted only through the UCM For switch calibration the Cut Profile is ON at the default setting of 20 This means that each time an Impact is recorded 20 of the Climb Window setting is added to the time remaining in the Climb Window see Figure 29 Note If there no Gain Threshold setting functions for both Cut alarm and Climb alarm detection change the Filter...

Страница 40: ...rm Figure 30 illustrates the Climb Alarm concept of a sustained attack within a specified time Figure 29 Understanding the Cut Alarm Figure 30 Understanding the Climb Alarm Threshold 10 time Window 30 10 20 5 15 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 reset counter Threshold 10 time Window 30 Cut Profile 20 add 6 seconds for each count 10 20 5 15 30 29 28 27 26 25 24 23 22 2...

Страница 41: ... with black jacket 300 m 984 ft reel when ordering allow for an overage of 5 30 m lead in cable G5SP0201 Non sensitive lead in cable with black jacket 30 m 98 ft reel FlexPI accessories termination splice kit C6KT2600 single zone termination splice kit cable ties GH0916 nylon tie wraps 1000 piece bag double loop bar ties 82 130020 steel bar ties 15 cm 6 in long 18 AWG 1000 pieces UCM software UCM ...

Страница 42: ...Page 42 FlexPI Product Guide ...

Страница 43: ...ontrols calibration adjustments via the Universal Configuration Module software application calibration adjustments via onboard switches adjustable filter settings frequency response Alarm outputs 2 form C relays rated 30 VDC 1 A max non inductive load 1 ALARM relay activates to signal sensor alarm condition 1 SUPERVISION relay activates to signal enclosure tamper condition cable fault condition p...

Страница 44: ...on Alarm LED Alarm LED UCM connected LED Enclosure door open LED Supervision mechanical enclosure tamper switch sensor wires lead in cable processor operation Temperature 0º to 70ºC 0º to 158º F Relative humidity 0 to 95 non condensing Frequency response switch selectable frequency response bands 100 300 Hz 300 900 Hz UCM adjustable frequency response band 100 900 Hz ...

Отзывы: