SENSORWORX SWX-201-B Скачать руководство пользователя страница 1

WIRELESS

CEILING MOUNT 

OCCUPANCY SENSOR

INSTALLATION & OPERATION INSTRUCTIONS

SPECIFICATIONS 

ELECTRICAL & WIRELESS

BATTERY TYPE

Requires one CR123(A) Lithium Battery

BATTERY LIFE

Designed for 10 Year Life  

  (under default settings)
Non-Volatile Memory (saves all 

  settings regardless of battery state)

Blink Warning @10% Life

RANGE

80’ line of site w/o obstruction (walls) 

40’ with obstruction (walls/floors)

FREQUENCY    

915 MHz ISM Band  

 

WIRELESS LINKING

Simple 3 sec. Push Button Process

SECURITY

All Wireless Data is Encrypted

ENVIRONMENTAL

OPERATING TEMP

32°F to 122°F (0°C to 50°C)

RELATIVE HUMIDITY

0-95% Non-Condensing,  

  Indoor Use Only

CODE COMPLIANCE

These sensors can be used to meet 
ASHRAE 90.1, IECC, & Title 24 energy 
code requirements.

PHYSICAL

SIZE

4.00” Diameter x 1.25” H 

(10.16 x 3.17 cm)

WEIGHT 

4.75 oz

COLOR

White

LED INDICATION

Motion Detection (when in Test Mode)

Wireless Linking (Pairing)

OPERATION

OPERATING MODES

Occupancy & Vacancy Modes
  Configured on Linked Controller

COMPATIBLE LOAD CONTROLLERS

SWX-851 Wall Switch 

SWX-950 Series Power Packs

WIRELESS TEST MODE

 Button Toggles On/Off
  Wirelessly Linked Loads

COVERAGE TEST MODE

White LED Illuminates Upon Detected
 Occupancy 

TIME DELAY OPTIONS

Configured at Load Controller(s)

1, 5, 10, 15, 20, 30 min.

FEATURES 

 

Ã

Pairs in Seconds with Wireless 
Controllers

 

Ã

Passive Infrared (PIR) Detection

 

Ã

360° Small Motion Coverage 
Pattern

 

Ã

10 Year Battery Life Design

 

Ã

Compact Size and Matte Finish

 

Ã

Four Contractor Friendly Mounting 
Methods

 

Ã

Mounting Nipple Attachment with 
Integrated Hole Saw

 

Ã

Convenient Test Modes 

OVERVIEW 

The 

SENSOR

WORX

®

 wireless ceiling mount occupancy sensor is a simple, yet reliable 

battery powered control solution. Preferred by contractors for their flexible mounting 
methods, 

SENSOR

WORX wireless sensors greatly reduce total installation time and 

wireless pairing fuss. Requiring just a few seconds per device, 

SENSOR

WORX wireless 

sensors can be linked to one or more wireless load controllers (such as the 

SWX-851

 

wireless wall switch, or a 

SWX-950 

series wireless power pack). Additionally, these 

sensors can be configured to work in applications with other wireless or wired ceiling, 
corner, or hallway sensors to provide extended coverage in large or irregularly shaped 
spaces. As with all 

SENSOR

WORX products, the latest passive infrared technology and 

digital signal processing techniques are used to provide unmatched occupant detection 
performance and energy savings.

MODEL NUMBERS

DESCRIPTION

SWX-201-B

WIRELESS CEILING MOUNT SENSOR, PIR, 360° SMALL MOTION, 
BATTERY POWERED

SWX-299-JP

CEILING SENSOR TRIM RING FOR MOUNTING TO SINGLE GANG 
MUDRING, HANDY BOX, OR 4” OCTAGON BOX

DETAILED OPERATION 

 

Ã

By default, every ~60 seconds the sensor transmits whether or not occupancy was detected during the previous period.

 

Ã

Referred to as the sensor’s “heartbeat”, this period can be reduced to ~30 seconds although this will decrease expected battery life.

 

Ã

If a sensor transmitted “unoccupied” at its last heartbeat, any new occupancy detection event will be transmitted immediately. 

 

Ã

If a sensor transmitted “occupied” at its last heartbeat, new occupancy events will only be transmitted at the heartbeat interval, thus conserving battery life.

 

Ã

The wirelessly linked wall switch load controller and/or power pack maintains a master time delay that is reset every time a linked sensor reports occupancy. Lights will be switched 
off once all linked sensors have continously reported unoccupied for the duration of the time delay.

BASIC OPERATION 

Sensors detect movement in the infrared energy that radiates from occupants as 
they move within the device’s field-of-view. Once occupancy is detected, the sensor 
immediately signals a wirelessly linked load controller (e.g. power pack) to switch on or 
dim up the connected lighting. At regular intervals, the sensor will retransmit its latest 
occupancy status such that the load controller can keep lights on for occupants during 
brief periods of inactivity, while returning the space to an energy saving lights off (or dim) 
state once no longer occupied.

Содержание SWX-201-B

Страница 1: ... or more wireless load controllers such as the SWX 851 wireless wall switch or a SWX 950 series wireless power pack Additionally these sensors can be configured to work in applications with other wireless or wired ceiling corner or hallway sensors to provide extended coverage in large or irregularly shaped spaces As with all SENSORWORX products the latest passive infrared technology and digital si...

Страница 2: ... an option if necessary Switching from a second location e g 3 way is achieved by linking a remote wireless wall switch to the wireless switch controller Both occupancy auto on and vacancy manual on operation are achievable in order to meet energy code requirements à Small Offices à Copy Rooms à Private Restrooms LARGE SPACES Multiple wireless sensors can be easily linked to a wireless power pack ...

Страница 3: ...ial occupancy as a replacement warning à Replacement batteries are available at most retailers or home centers where batteries are sold or from SENSORWORX MOUNTING BRACKET CHASE NIPPLE BATTERY COMPARTMENT BATTERY COMPARTMENT BATTERY COMPARTMENT LOCK NUT CHASE NIPPLE LOCK NUT LOCKING 3 POSITION TILT ADJUSTMENT MOUNTING BRACKET LOCKING 3 POSITION TILT ADJUSTMENT SERRATED END FOR CUTTING THROUGH CEIL...

Страница 4: ...OR POWER PACK SWX 201 B HOLD FOR 3 SEC SWX 851 HOLD FOR 3 SEC SWX 950 HOLD FOR 3 SEC SWX 851 PRESS ONCE SWX 950 PRESS ONCE OR OR CONFIGURATION SENSOR HEARTBEAT TIME The period between transmissions of a wireless sensor is referred to as the sensor s heartbeat For best battery life performance it is recommended that the default heartbeat time of 1 minute be used However if a linked load controller ...

Страница 5: ...To test coverage wait until lights turn off then walk into range of sensor While in test mode the LED will blink when it transmits an occupied signal maximum of once every 4 seconds After 10 minutes the unit will automatically exit test mode Note Once test mode has been inititated from a linked sensor the linked controller will ignore all other sensors until a new sensor initiates test mode or the...