8
Picture 2.1
Electric connection and sealing of
MS-K-500-3
signal device should be executed in
the following order:
-
Screw out the nut 13 from the cable fitting 3.
-
Open the exterior panels 5.
-
Screw out screws 14 (4 pcs.) on the cover fixtures.
-
Flip put the housing 2 cover.
-
Remove external cable insulation within 20 ... 30 mm of its length, remove wires
insulation within 5 ... 7 mm of their length. 7 mm.
-
Put on the nut 13 on the cable.
-
Insert cable into the cable fitting 3.
-
Connect the barbed wires ends to a terminal clamp 8 in accordance with marking
15.
-
Tighten nut 13.
WARNING! The cable must not move or turn in rubber packing.
-
Flip in (close) the housing 2 cover.
-
Screw out screws 14 (4 pcs.) on the cover fixtures.
-
Close the exterior panels 5.
-
Electric connection and sealing of MS-K-500-3 signal device should be executed
in the following order (see picture 1.2.):
-
Remove the insulation from the cable within 5 ... 7 mm of its length.
-
Connect the barbed wires ends to a terminal clamp 7 in accordance with marking
9.
2.3.5 After wiring it is required to configure signal device in accordance with a spe-
cific application. It is necessary to check the accordance of settings recorded in configura-
tion data sheet for specific application and, if necessary, adjust the configuration. Configu-
ration is made in accordance with cl. 2.4.2. All changes must be recorded in configuration
data sheet.
2.3.6 Check operational capability after configuration. For this the correct displaying
of all measured and calculated (by all transducers) values should be checked. Then, if nec-
essary, using transducer emulation mode it is required to check the operation of executive
mechanisms.
2.4 Used items
2.4.1 General information
Device usage includes connected units features display and adjustment of signal
and other devices in SENS line. Viewing of parameters
In operation mode the signal device displays the device address, designation, value
and parameter measuring units(see picture 2.2). The information line determining the cer-
tain parameter designation shall be displayed in the operation mode.
Viewing parameters
Liquid level
21. h
м
3.4036
Converter address
Units
Parameter value
Information
Parameter designation