Doc#: 1460002, Rev C
Operation Manual, SEC Millenium Hydrocarbon Gas Detector
Page
10
of
14
IV. CALIBRATION
SEC MILLENIUM
The SEC MILLENIUM is factory calibrated; zeroed and spanned.
Unlike catalytic sensors it does not require
routine span gas calibration to ensure proper operation.
The SEC MILLENIUM can be calibrated for almost any hydrocarbon using a calibration gas of the
hydrocarbon that is to be detected (target gas). The SEC MILLENIUM is required to be spanned with gas
only one time with the target gas. Typically this is done at the factory, but it is possible to field span the
device by connecting the SEC MILLENIUM to a computer and using a software package provided by SEC.
Please contact the factory for further details.
A typical field calibration only requires the use of zero air (or 99.99% nitrogen).
If the sensor is located in an
area that is known to be free of the hydrocarbon gases then ambient air can be used as a zero reference.
If zero air is used for the calibration, there is a fitting on the bottom of the sensor for a 1/8” ID tubing
connection.
Before beginning calibration use the SEC MILLENIUM Insulation Tube to cover outer cylinder holes and
connect a clean air source to the sensor’s calibration port for a minimum of 3 minutes. To enter into the
calibration mode the calibration wire must be connected to negative (common of the power supply) for ten
(10) seconds, upon release the sensor will automatically enter the zero calibration routine. The electronics
will automatically adjust the sensor’s signal to the new zero reference level. (Applying span gas is not
necessary because of the SEC MILLENIUM’s unique software algorithms). During the zero calibration
routine, the current output of the SEC MILLENIUM will go to 2.2 mA. Although this can be accomplished
manually, installation of a switch (contact closure) can accomplish the zeroing procedure. It is
recommended that this switch be a momentary type switch to prevent it from inadvertently being left in the
calibrate position. If after 20 seconds the calibration lead has not been removed from common, the SEC
MILLENIUM will ignore the signal and continue operation as normal.
The SEC MILLENIUM can be spanned in the field if the customer wishes to change the target hydrocarbon
gas. Please contact factory for additional equipment information and pricing for SEC PC IR Link Package)
V. MAINTENANCE
The SEC MILLENIUM does not normally require cleaning of the optics. However if the unit is operating in a
very dirty or dusty environment the optical path might become obscured. If the obscuration is severe enough
to affect the unit’s accuracy, the unit will activate an “Optics Fault”. To clear an Optics Fault, first try a
calibration. If the calibration does not correct the fault condition, try to clean the optics. The outer barrel
(tube with two sets of holes) can be removed (unscrewed) to inspect the cleanliness of the hydrophobic
filter. The hydrophobic filter is a Teflon coated stainless steel mesh that keeps moisture and particulates out
of the optical path. A setscrew holds the filter to the MILLENIUM’s housing. Once the hydrophobic filter is
removed, the internal waveguide tube should be inspected for cleanliness. The waveguide and waveguide
collar can be removed by inserting rigid instruments such as Allen wrenches into one hole of the waveguide
and one hole of the collar. Turning the two instruments in opposite directions will loosen the waveguide
allowing the collar to be screwed down on to the waveguide until it can be removed from the SEC
MILLENIUM housing. This will allow the windows of the SEC MILLENIUM to be cleaned. Dust can be
removed using compressed air. Hard or oily deposits can be removed using Isopropyl alcohol and cotton
tipped swabs. Wipe any film or residue or film left by the alcohol on the windows with a clean dry cotton
swab. The internal surface of the electro-polished wave-guide tube can be cleaned the same way. Be
careful not to leave any particles of the cleaning swab in the waveguide. The waveguide holes can collect
pieces of the cleaning swab. After reassembling the unit (the waveguide and collar should be very tight to
both ends of the SEC MILLLENIUM housing after installation. Once the unit is completely reassembled and
power is reapplied, the SEC MILLENIUM must be calibrated. Refer to the calibration section of this manual.
Содержание SEC 3000
Страница 15: ...Doc 1460003 Rev A Operation Manual SEC 3000 Electro Chemical Gas Sensor Page 12 of 13 ...
Страница 54: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 4 SEC 3100 SEC Millenium Mounting ...
Страница 55: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 5 SEC 3100 SEC 3000 Mounting ...
Страница 56: ...TB 1 J1 TB 2 J2 1 6 1 6 1 4 1 6 TB 5 J5 TB 6 J6 ...
Страница 100: ...Operator Manual Page 39 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707 ...
Страница 101: ...Operator Manual Page 40 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707 ...
Страница 148: ...SEC 3120 Wiring TB 1 P3 TB 2 P6 1 6 1 6 1 2 3 4 1 2 3 4 7 6 5 4 3 2 1 TB 3 P1 TB 4 P5 ...
Страница 156: ......
Страница 158: ......
Страница 159: ......
Страница 160: ......
Страница 161: ......
Страница 399: ...SEC P N 1460014 Rev ECO A 000209 Page 11 of 26 ...
Страница 400: ...SEC P N 1460014 Rev ECO A 000209 Page 12 of 26 ...
Страница 431: ...Part Number 1460005 Revision C ...
Страница 433: ...Part Number 1460005 Revision C ...
Страница 434: ...Part Number 1460005 Revision C ...
Страница 435: ...Part Number 1460005 Revision C ...
Страница 448: ...10 VII Drawing Section Figure Title Figure 1 Wiring Diagram SEC MILLENIUM Figure 2 SEC Sensor Separation Kit ...
Страница 473: ...10 VII Drawing Section Figure Title Figure 1 Wiring Diagram SEC MILLENIUM Figure 2 SEC Sensor Separation Kit ...