
P 1/2 SW_IN_TC-169-1_test-lamp_for-210_series_flame_detectors_v1.docx
Test Lamp TC-169/1 for 210-series
Flame Detectors, non EX
•
Specifications
•
User Guide
•
Instructions
1. Description
The non EX Sense-WARE TC-169/1 Flame Detector Test Lamp activates 210-series Flame Detectors from Sense-
WARE; the UV/IR-210/1, the UV-185/5 and the IR3-109/1. For all models the detection range is 4 meters (13 ft). The
TC-169/1 Test Lamp is non EX, suitable for use in safe areas only.
Warning:
The TC-169/1 Test Lamp is only compatible with the 210-series Flame Detectors of Sense-WARE. The Test Lamp is
not suitable for Flame Detectors of other brands.
2. Specifications
Test Lamp:
Test range
up to 4 m (13 ft)
Use
10-15 minutes under optimal conditions and continuous use
Housing; material, dimensions / weight
ABS/PC, 160 x 140 x 260 mm (6.5
x 5.5 x 10 “); 0.65 kg (1.4 lbs)
Ingress protection rating
IP30
Temperature range
+4 to +40
0
C (+39 to +104
0
F)
Carrying case:
Polypropylene, inlay: Polyurethane
Dimensions / weight
400 x 190 x 310 mm (16 x 8 x 12”); 2 kg (4.5 lbs)
Battery:
Sealed Lead Acid, 12 V / 2.7 Ah
dimensions / weight
103 x 70 x 46 mm (12.5 x 9 x 8.5
“); 1 kg (2.2 lbs)
Charger
, (Adapter):
100-240 Vac, 1600 mA switching with pins for US, EU, GB and AU
dimensions / weight
148 x 100 x 45 mm (6 x 2.5 x 2 “); 0.25 kg (0.5 lbs)
Light bulb:
Broad Band, 12 Vdc / 100 W
dimensions / weight
50 x 20 (D) mm
(2 x 1(D) “); 0.03 kg (0.07 lbs)
CE declaration:
See website
Country of Origin / Statistic Numbers
The Netherlands, EU (IS): 8531 10 30, USA (HS): 853110 0045
3. Safety instructions
1. Only suitable for Sense-WARE 210-series Flame Detectors: UV/IR-210/1, UV-185/5 and IR3-109/1.
2. The life time of the battery is negatively influenced if you use the Test Lamp continuously longer than 10 minutes
and in one go. The Test Lamp will automatically stop working after 30 seconds.
3. The Test Lamp has a protective grate which should not be removed. Warning, after use the grate may be hot. Do
not stick objects through the grate.
4. Store the Test Lamp clean and dry. A dirty reflector will reduce the test range.
5. Do not use the Test Lamp in wet conditions.
6. Keep away from children. Do not point directly at eyes from a short distance. Do not look directly into the light.
7. Do not use when damaged. Do not open the lamp, send it back for repair. Contact Sense-WARE for details.
8. Do not throw the unit in a fire. The battery could explode when exposed to intense heat.
9. The sealed lead battery has a lifetime of several years. Please ask your local city official how to dispose the unit.
10. Make sure testing of the Flame Detectors does not activate unwanted alarm signals.
11. Use in safe areas only.
12. Dispose the items in accordance with the WEEE directive.