Universal Test Lamp T-229/4P for
UV, IR and UV/IR Flame Detectors
•
Specifications
•
User Guide
•
Instructions
1. Description
The Sense-WARE T-229/4P Flame Detector Test Lamp activates UV, IR and UV/IR Flame Detectors which detect in
the 185-235 nm UV and 4.4 µ IR frequency ranges. For UV only detectors the maximum distance is up to 8 meters
(26 ft) in the continuous mode. The test range for IR and UV/IR detectors is up to 4 meters (13 ft). Most IR Flame
Detectors have an extra alarm criterion; analyzing the flicker frequency of a fire. The Test Lamp T-229/4P can be put
into the pulse mode by means of a selection switch on the left side of the Test Lamp. The lamp then emits pulsed
energy with a frequency of approx. 2 Hz. After the alarm delay time the IR or UV/IR Flame Detector will activate.
Not suitable for:
IR/IR- (dual IR), IR/IR/IR (IR3 or triple IR) Flame Detectors, whether or not in combination with a
UV sensor.
For use in safe areas only.
2. Specifications
Test Lamp:
Test range UV Flame Detectors
up to 8 m (26 ft) in continuous mode, up to 4 m (13 ft) in pulse mode
Test range IR and UV/IR Flame Detectors
up to 4 m (13 ft)
Use
10-15 minutes under optimal conditions and continuous use
Housing; material, dimensions / weight
ABS/PC, 160 x 140 x 260 mm (6.5
x 5.5 x 10 “); 0.65 kg (1.4 lbs)
Ingress protection rating
IP30
Temperature range
+4 to +40
0
C (+39 to +104
0
F)
Carrying case:
Polypropylene, inlay: Polyurethane
Dimensions / weight
400 x 190 x 310 mm (
16 x 8 x 12”); 2 kg (4.5 lbs)
Battery:
Sealed Lead Acid, 12 V / 2.7 Ah
dimensions / weight
103 x 70 x 46 mm (12.5 x 9 x 8.5
“); 1 kg (2.2 lbs)
Charger
, (Adapter):
100-240 Vac, 1600 mA switching with pins for US, EU, GB and AU
dimensions / weight
148 x 100 x 45 mm (6 x 2.5 x 2 “); 0.25 kg (0.5 lbs)
Light bulb:
Broad Band, 12 Vdc / 100 W
dimensions / weight
50 x 20 (D) mm (2 x 1(D) “); 0.03 kg (0.07 lbs)
EU declaration:
See website
Country of Origin / Statistic Numbers
The Netherlands, EU (IS): 8531 10 30, USA (HS): 853110 0045
3. Safety instructions
1. The life time of the battery is negatively influenced if you use the Test Lamp continuously longer than 10 minutes
and in one go. The Test Lamp will automatically stop working after 30 seconds.
2. The Test Lamp has a protective grate which should not be removed.
Warning, after use the grate may be hot. Do
not stick objects through the grate.
3. Store the Test Lamp clean and dry. A dirty reflector will reduce the test range.
4. Do not use the Test Lamp in wet conditions.
5. Keep away from children. Do not point directly at eyes from a short distance. Do not look directly into the light.
6. Do not use Test Lamp when damaged. Do not open the lamp, send it back for repair. Contact Sense-WARE for
details.
7. Do not throw the unit in a fire. The battery could explode when exposed to intense heat.
8. The sealed lead battery has a lifetime of several years. Please ask your local city official how to dispose the unit.
9. Make sure testing of the Flame Detectors does not activate unwanted alarm signals.
10. Use in safe areas only.
11. Dispose the items in accordance with the WEEE directive.
4. Warranty
If not explicitly mentioned in this instructions, the warranty clauses of the Orgalime S2012 delivery terms and
conditions apply. For this item a warranty of 12 months after supply is applicable (for stockholding distributors 18
months) for defects in the material, considering normal use and maintenance. SENSE-WARE will, under these
circumstances and during the warranty period, repair and replace parts, free of charge of products which are returned
according of our instructions. All replaced parts become property of SENSE-WARE. The warranty is only valid for
companies which directly purchased the goods from SENSE-WARE and cannot be transferred.
Standard Carrying Case