Page 10
12LPC15 Manual
INSTALLATION
Mount Inverter
WARNING: Power inverters produce hazardous voltages. To avoid risk of harm or fire, the unit must be
properly installed.
WARNING: Power inverters should not be mounted in a location that may be exposed to rain or spray.
WARNING: Power inverters should not be installed in a zero-clearance enclosure.
WARNING: Power inverters contain a circuit breaker and capacitor that may produce a spark upon connection
or during normal operation. Do not mount in a confined battery or gas compartment.
Installation Tools
•
Wire Termination Crimper
•
Cable-Ties
•
Drill
•
#2 Phillips Screw Driver (with a magnetic end)
•
Slotted Screw Driver
•
Tape Measure
•
Wire Cutters
•
Needle Nose Pliers
•
Wire Strippers
Inverter Mounting Recommendations
NOTE: The inverter mounting location should provide adequate ventilation and clearance to maintain room
temperature during operation. At least ½” of clearance is required on all sides except the bottom.
1.
Locate a suitable, secure mounting surface as close to the batteries as possible without being in the same
compartment.
2.
Mount the inverter using four ¼-20 steel bolts, flat and lock washers, and nuts. The length of the bolts should
be equal to the thickness of the mounting surface plus ¾”.
Figure 2 Mounting for All Models (Inches)