SENS EnerGenius® DC Compact Technical Manual
48
2
0x02
AC1 Breaker
The AC breaker is OPEN or has tripped. Only available with Breaker
Status option.
3
0x03
Unused
Unused
4
0x04
Unused
Unused
5
0x05
DC SPD
The DC supplementary surge protector has expired and needs
replacement.
6
0x06
DC Breaker
The DC breaker is OPEN or has tripped. Only available with Breaker
Status option.
7
0x07
Unused
Unused
8
0x08
Unused
Unused
9
0x09
Unused
Unused
10
0x0A
Unused
Unused
11
0x0B
System
Display Board
This device is configured as a system display board. It will present
information for the entire system, even if devices are not in its unit.
12
0x0C
Unused
Unused
13
0x0D
Sensbus
Inactive
No other devices are found on SENSBus.
14
0x0E
Unused
Unused
15
0x0F
Unused
Unused
16
0x10
Unused
Unused
17
0x11
Unused
Unused
18
0x12
No Power
Board Data
No module power boards are found on SENSBus.
11.10.
Accessory Assigned Channel Alarms Bit Definition
Bit Address
Name
Description
Decimal
Hex
0
0x00 Invalid Config
The configuration of one or more power modules in the unit is
invalid.
1
0x01 Individual Module Fault
A power module in the unit has faulted.
11.11.
Writable Control Flags (Coils)
Single coil writes: 0xFF00 for ON, 0x0000 for OFF
Address
Description
Details
Decimal
Hex
16
0x010
Start/stop manual boost
ON to start, OFF to stop
17
0x011
Reset periodic boost charge schedule
ON to reset schedule, OFF is no-op
18
0x012
Start/stop battery check
ON to start, OFF to stop
19
0x013
Reset periodic battery
ON to reset schedule, OFF is no-op
20
0x014
Clear battery check failure
ON to reset alarm, OFF is no-op
21
0x015
Not applicable
Not applicable
22
0x016
Force DC Startup
ON to start, OFF to stop
23
0x017
Reset Latched Alarms
ON to reset alarm, OFF is no-op