background image

SENS

®

 DC PowerCab

 120 

Installation, Operation, & Maintenance Manual 

Содержание DC PowerCab 120

Страница 1: ...SENS DC PowerCab 120 Installation Operation Maintenance Manual...

Страница 2: ...Industrial Circle C C Power Inc Longmont Co 80501 395 Mission Street www sens usa com Carol Stream IL 60188 Technical Support Phone 303 678 7500 or 800 742 2326 Email service sens usa com SENS the SE...

Страница 3: ...0 6 2 System Grounding 10 6 3 AC Input 10 6 4 DC Output 10 6 5 Optional AC Output 11 6 6 Optional LVD 11 6 7 General Specifications 11 7 Installation 13 7 1 Preparation 13 7 1 1 Equipment Inspection 1...

Страница 4: ...during the installation and maintenance of the system 1 1 MANUAL SYMBOLS Warning Caution Indicates information provided to protect the user against personal injury safety hazards and or possible equi...

Страница 5: ...ons are C UL listed Sales support for existing or future equipment needs are provided by our technical sales staff For all technical sales and service related questions please call our office line at...

Страница 6: ...ment System installation and maintenance should always be performed with heavily insulated tools It is also recommended to wear rubber gloves boots and use insulating mats to stand on when working on...

Страница 7: ...ns and possible death all jewelry including bracelets rings and watches must be removed prior to installing or servicing this system Do not open or mutilate batteries Opened or severely damaged batter...

Страница 8: ...icable notations on the delivery receipt before signing and file a damage report with the carrier 4 3 CONCEALED DAMAGE Within 3 to 30 days of receipt depending on courier unpack the system and check f...

Страница 9: ...upply charger storage battery string and DC distribution to load center In addition to the charger battery distribution panel and cabinet PowerCab can be optionally equipped with Additional DC distrib...

Страница 10: ...C 50 60 Hz 1 240 VAC 60 Hz 1 115 120 208 230 240 VAC 60 Hz 1 115 120 208 230 240 VAC 50 60 Hz 1 400 VAC 50 60 Hz 1 480 VAC 60 Hz 1 6 4 DC OUTPUT DC Output Voltage Options include 24 volt nominal 12 ce...

Страница 11: ...s the systems batteries will discharge in order to provide the necessary backup power to the load If the DC PowerCab 120 is equipped with the Low Voltage Disconnect LVD feature the system load will be...

Страница 12: ...e as suggested by NEC and or all applicable national and local codes The battery cabinet does not require rear access or rear clearance Under certain conditions batteries can vent potentially explosiv...

Страница 13: ...and local codes The battery cabinet does not require rear access or rear clearance Before proceeding with system installation be sure to review and understand all of the SAFETY PRECAUTIONS in this man...

Страница 14: ...located on the bottom panel of the cabinet in the front right hand corner Wire should be sized per NEC and or all applicable national and local codes 7 2 4 AC DC CONNECTIONS Do not attempt to unpack o...

Страница 15: ...at the battery string output and the charger DC output are connected to the breakers on the panelboard specified in the system schematic drawing Assure that these two breakers are in the off open posi...

Страница 16: ...move the bad battery Before proceeding with system maintenance be sure to review and understand all of the SAFETY PRECAUTIONS in this manual Verify that the Battery Main breaker on the panelboard and...

Страница 17: ...t door to verify the cabinet wiring 10 Reconnect the cables to battery and make sure the connections are properly torqued 11 Reconnect any removed string jumpers and make sure the connections are prop...

Страница 18: ...SENS DC PowerCab 120 8 24 2017 18 755 00129 R04 9 REFERENCE MATERIALS Figure 1...

Страница 19: ...SENS DC PowerCab 120 8 24 2017 19 755 00129 R04 Figure 2...

Страница 20: ...1 K1 assignment alarm category 1 Err OFF Device error at K1 r1 U ON Undervoltage K1 r1 U OFF Overvoltage K1 r1 Hz OFF Underfrequency K1 r1 Hz OFF Overfrequency K1 1 S AL OFF Start with alarm during t...

Страница 21: ...n alarm state r1 K1 assignment alarm category 1 Err OFF Device error at K1 r1 U ON Undervoltage K1 r1 U OFF Overvoltage K1 r1 Hz OFF Underfrequency K1 r1 Hz OFF Overfrequency K1 1 S AL OFF Start with...

Страница 22: ...K1 assignment alarm category 1 Err OFF Device error at K1 r1 U ON Undervoltage K1 r1 U OFF Overvoltage K1 r1 Hz OFF Underfrequency K1 r1 Hz OFF Overfrequency K1 1 S AL OFF Start with alarm during t t...

Страница 23: ...SENS DC PowerCab 120 8 24 2017 23 755 00129 R04 10 WARRANTY For warranty information please go to www sens usa com warrantyrepair...

Страница 24: ......

Отзывы: