6.6.2 Settings
The output can be scheduled to be configured at a multiple of the base-interval. In the event that the
Interval is set to a number higher than 1, the output will only checked and configured on the next output
interval. This can be used to create a pulsed output that may be useful in driving alert indicators or in
allowing attached devices to time to cool down.
The Mode setting can be used to configure the output with alternate functions as an analog or digital
input. In input mode, the same settings as are associated with Input 2 apply.
The output can be configured to activate when any of the peripherals report an exception (warning, alarm
or alert) as a result of a measurement and can be set to remain on only as long as the warning or alarm is
active or to hold on for a time after the warning or alarm has gone away.
Note The output will be configured at each output interval. The hold-time is how long the output is kept
enabled after the exceptions are cleared.
A full list of settings for the output is given in the table at the end of this chapter.
6.7 External Sensor Settings
A full list of settings for external sensors is given in the table below.
Name
Item
Function
Range
Unit
Internal
Reference
Input 1
Name
text
A name for the input that is meaningful
to the user.
25 chars
input1.name
Interval
integer
The number of base intervals after
which the input is sampled. A value of
1 means that the input is collected every
base interval. Set to 0 to disable.
0
to
10000
input1.interval
Mode
preset
Specifies the function of the IN1 termi-
nal. The calibration, warnings and
alarms are applied to this mode.
input1.mode
Digital 1
Digital
Threshold
decimal
A threshold against which the input is
compared to determine if the input
state is ON or OFF.
0 to 30
Volts
input1.digital.threshold
Digital
Hysteresis
decimal
Once the input is in a certain state,
hysteresis is the amount by which the
input has to change before moving to
the other state.
0 to 20
Volts
input1.digital.hysteresis
Count Hours
boolean
Counts the number of hours the digtial
input is ON (above threshold).
input1.digital.count_hours
Digital
Change Alert
boolean
Sets whether a change in digital state
generates an alert.
input1.digital.alert.enable
Analog 1
Calibration
text
Calibration parameters for Analog 1.
Refer to user guide.
30 chars
input1.cal
ORB User Guide, Release 1.1
72
Chapter 6. External Sensors
Содержание ORB-X1-G
Страница 1: ...ORB User Guide Release 1 1 Senquip Sep 14 2020...
Страница 2: ......
Страница 16: ...ORB User Guide Release 1 1 10 Chapter 1 Introduction...
Страница 44: ...ORB User Guide Release 1 1 38 Chapter 3 Power Supply...
Страница 50: ...ORB User Guide Release 1 1 44 Chapter 4 General Setup...
Страница 86: ...ORB User Guide Release 1 1 80 Chapter 6 External Sensors...
Страница 92: ...ORB User Guide Release 1 1 86 Chapter 7 Network Connection...
Страница 98: ...ORB User Guide Release 1 1 92 Chapter 8 Endpoint Setup...
Страница 110: ...Figure 10 2 Dimensioned side view ORB User Guide Release 1 1 104 Chapter 10 Mechanical Speci cation...
Страница 111: ...Figure 10 3 Dimensioned side view including mounting brackets ORB User Guide Release 1 1 10 1 Mechanical drawings 105...
Страница 116: ...ORB User Guide Release 1 1 110 Chapter 10 Mechanical Speci cation...
Страница 130: ...ORB User Guide Release 1 1 124 Chapter 12 Troubleshooting Guide...
Страница 134: ...ORB User Guide Release 1 1 128 Index...
Страница 136: ......