ENGLISH - 1/8
MI000224-E
Z112A
Amplifier with pulse divider for ON-OFF sensors
EN
Pulse input for all the most common sensors: mechanical contact,
reed, 2 and 3 wire npn with 12Vdc and 24Vdc power supply, 3 wire
pnp with 24Vdc power supply, NAMUR, photoelectric.
Max frequency 400 Hz.
Divider circuit programmable by dip switch from 1 to 256.
Adjustment of pulse duration at output from 100 msec to 500 msec by
means of trimmer on front panel.
Relay output with 1 SPDT changeover with capacity 5 A 250 Vac
(resistive load).
Front panel LED indication of power on and relay energised.
Insulation between power supply and inputs: 1500Vac, insulation to
output > 3000Vac.
GENERAL CHARACTERISTICS
TECHNICAL SPECIFICATIONS
19 – 40 Vdc, 19-28 Vac 50-60Hz, max 2.5W.
Pulses: mechanical contact, reed, 2 and 3 wire npn with
12Vdc and 24Vdc power supply, 3 wire pnp with 24Vdc
power supply, NAMUR, photoelectric.
Max frequency 400 Hz.
Relay with 1 SPDT changeover with capacity 5 A 250 Vac
(resistive load).
Temperature: 0..50°C, Humidity - min:30%, max 90% at
40°C non condensing (also see section Installation
standards).
EN61000-6-4 (electromagnetic emissions, industrial ambient)
EN61000-6-2 (electromagnetic immunity, industrial ambient)
EN61010-1 (safety)
Power supply:
Inputs:
Outputs:
Ambient conditions:
The instrument
conforms to the
following standards: