Seneca Z-KEY Скачать руководство пользователя страница 2

 

          

MI00369-3-EN 

ENGLISH2/8

 

1 PRELIMINARY WARNINGS 

 

The full content of this manual must be read before performing any operation. The module 
must only be used by qualified electricians. Specific documentation is available at 

www.seneca.it

 

 

The module must be repaired and damaged parts replaced by the Manufacturer. The product 
is sensitive to electrostatic discharges.  Take appropriate measures during any operation. 

 

The warranty is null and void in the event the module or devices supplied by the 
Manufacturer, necessary for correct operations, are improperly used or tampered with and, in 
any case, if the instructions contained in this manual were not followed. 

2 PRELIMINARY USE INSTRUCTIONS 

 

Obstructing ventilation slots with any object is prohibited. 
Installing the module next to devices that generate heat is prohibited. 

 

3 GENERAL SPECIFICATIONS 

CPU ARM 32 bit 

Possibility of configuration via Web-server. 

Micro SD card slot, Max 32 GB (Optional) for custom webserver and FTP server pages. 

One Ethernet 100 Mbits/s port 

One RS485 port. 

One RS485/RS232 commutable port. 

One USB port. 

1500 V

 power insulation with respect to the remaining low voltage circuits. 

Facilitated power and serial line cabling via Seneca bus that can be housed in the IEC EN 60715 omega 
guide. 

Pull-out terminals, section 2.5 mm

2

Power indication, RS485/RS232 Rx and Tx, ETHERNET connection and activity on SD card via LED on 
front panel. 

Modbus Gateway from Modbus TCP to Modbus RTU: Ethernet / RS485 communication to remotely 
control modules connected to the Modbus RTU ports with the possibility of setting RS485 ports in 
Modbus master, Modbus slave mode. 

Modbus TCP-IP / Modbus RTU bridge in real time. 

Remote serial port (COM port) transparent to protocol. 

Baud rate for Modbus RTU settable from 1200 to 115200 baud. 

Firmware update via Web Server/ FTP Server / microSD card. 

POSSIBLE CONFIGURATIONS 

- BRIDGE FROM MODBUS TCP-IP TO MODBUS RTU 

- GATEWAY FROM MODBUS TCP-IP TO MODBUS RTU (PORT 1 AND PORT 2 MODBUS MASTER) 

- GATEWAY FROM MODBUS TCP-IP TO MODBUS RTU (1 PORT MASTER AND 1 PORT SLAVE) 

- GATEWAY FROM MODBUS TCP-IP TO MODBUS RTU (2 PORT SLAVES) 

- REMOTE SERIAL COM PORT 

 

 

 

Содержание Z-KEY

Страница 1: ...ca srl Registered offices Via Austria 26 35127 Z I Padua IT Tel 39 049 8705355 8705355 Fax 39 049 8706287 Website www seneca it Mail Technical support support seneca it Product information sales seneca it This document is property of SENECA srl Copies and reproduction are prohibited unless authorised The content of this document corresponds to the described products and technologies Indicated data...

Страница 2: ...rver and FTP server pages One Ethernet 100 Mbits s port One RS485 port One RS485 RS232 commutable port One USB port 1500 V power insulation with respect to the remaining low voltage circuits Facilitated power and serial line cabling via Seneca bus that can be housed in the IEC EN 60715 omega guide Pull out terminals section 2 5 mm2 Power indication RS485 RS232 Rx and Tx ETHERNET connection and act...

Страница 3: ...ave protocol RS485 IDC10 rear connector Maximum Baud rate 115k Modbus RTU master Modbus RTU slave protocol RJ45 Ethernet connector on front 100 Mbit s Max distance 100 m with auto switch USB Plug in lateral micro USB Power supply Voltage 11 40 V 19 28 V 50 60 Hz Consumption Typical 1 5W 24 V Max 2 W 24 V Operating conditions Temperature 25 C 50 C Humidity 30 90 to 40 C non condensing Altitude up t...

Страница 4: ... the two hooks on the side of the IDC10 rear connector as illustrated in fig 1a Removal from IEC EN 60715 DIN guide As illustrated in figure 1b 1 Move the two side hooks outward from the module assisted by a screwdriver 2 Extract the module from the guide 6 ELECTRICAL CONNECTIONS IDC10 rear connector POWER AND PORT 1 The illustration indicates the meanings of the various IDC10 connector pins if si...

Страница 5: ... indication of the RS485 connection polarity is not standardised and in some devices may be inverted Serial port 2 RS485 SW2 ON Z KEY has a serial port that can be set with the SW2 switch If the SW2 switch is ON then terminals 10 11 12 have the RS232 COM 2 available The illustration shows how to complete connections The RS232 interface is fully settable RJ45 Ethernet connector on front Z KEY has a...

Страница 6: ...ngs RS232 or RS485 settings on terminals 10 11 12 serial port 2 KEY RS232 ON RS485 OFF 7 INDICATIONS VIA LED ON FRONT PANEL LED STATUS LED meaning TX1 Red Flashing Data transmission on port 1 RS485 RX1 Red Flashing Data receipt on port 1 RS485 TX2 Red Flashing Data transmission on port 2 RS485 RX2 Red Flashing Data receipt on port 2 RS485 PWR Green On Device powered SD Red Flashing Access to micro...

Страница 7: ...Material recycling will contribute to the preservation of natural resources To receive further information please contact your local waste disposal service centre or product dealer Z KEY can be fully set up via integrated web server Product programming tools can be downloaded free of charge at www seneca it in the Z KEY section To access settings open the maintenance page in a browser at the Z KEY...

Страница 8: ...MI00369 3 EN ENGLISH8 8 ...