RESETTING THE DEVICE TO ITS FACTORY CONFIGURATION
11.
The factory configuration removes all configured tags and resets all parameters to default.
To reset the device to the factory configuration it is necessary to follow the procedure below:
1)
Remove power from the device
2)
Set all DIP switches to ON
3)
Power up the device and wait at least 10 seconds
4)
Remove power from the device
5)
Set all DIP switches to OFF
6)
At the next restart the device will have loaded the factory configuration
EXCEL TEMPLATE
12.
In the case of entering many variables, it is convenient to use the excel template downloadable from the
Seneca website in the Z-KEY-P section.
It is possible to insert the tags and then export them to the device's webserver.
MODBUS TCP-IP SERVER AND MODBUS PASS-THROUGH
13.
By querying Z-KEY-P through port 502 at slave address 254, it responds with the values of the tags in real-
time.
By querying Z-KEY-P via port 502 at the slave address from 1 to 253, the device converts Modbus TCP-IP
requests into Modbus RTU (Pass-Through mode)
Address 255 is reserved for device configuration.