English
23
•
Plug and socket connections according to
IEC 62196
• The charging system is only intended for opera-
tion in TT, TNC and TNCS networks. The charging
system must not be operated in IT networks.
• The charging system is not suitable for charging
vehicles with batteries which produce gas (such
as lead-acid batteries).
•
The charging system is intended exclusively for
stationary installation. The charging system is
suitable for outdoor installation.
• Only persons who have read the operating
instructions may operate and use the charging
system.
• The electrical installation, start-up, and main-
tenance of the charging system may only be
performed by qualified electricians who have
been correspondingly authorised by the operator.
•
The qualified electricians must have read and
understood the device documentation and must
comply with its instructions.
Requirements regarding the qualification
of electricians
Knowledge of and compliance with the five safety
rules for working with electrical installations:
1. Isolate.
2.
Secure against reactivation.
3.
Check absence of voltage.
1.
SAFETY INFORMATION
Please observe the following information for safe
set-up and operation of the Wallbox.
1.1
Information for the operator and
users of the charging system
• Read the operating instructions before putting
the charging system into operation.
•
Ensure that all persons working on or using
this charging system have read the operating
instructions.
•
Make sure to follow the regulations and instruc
-
tions for safe working.
• Keep the device documentation in a safe place
where it is always accessible to charging system
users.
• Ensure that unauthorised persons cannot access
the charging system.
1.2
Intended use
The charging system is intended to be used in
the private and semi-public sector, e.g. on private
property, company parking areas or machinery and
equipment yards. Do not use the charging system
in places where potentially explosive or combustible
substances (such as gases, liquids or dusts) are
stored or present. The charging system is intended
exclusively for charging electric vehicles.
•
Mode 3 charging according to IEC 61851-1
Designation
Technical Specifications
Regulations
EN 61851-1; EN 61439-7 (AEVSC)
Charging capacity type 3
up to 11 kW
Nominal voltage
230 V / 400 V / 1/3 AC
Nominal current
up to 16 A adjustable from 6 A to 16 A in 2 A increments
Nominal frequency
50 Hz
Connection method
Spring clip method
Charging connection/charging coupler
Type 2
Length of charging cable
7.5 m
Operation/status information
LED Front Panel
Protection rating
IP54
Mechanical impact protection
IK08
Residual current detection
DC 6 mA (IEC62955)
Ambient temperature
-25 °C to +40 °C
External Design
Wall mounted | Stele mounted
Protection class
I
Overvoltage category
III
Pollution degree
3
Sizes
(HxWxD) 410 mm x 295 mm x 114 mm
Weight
approx. 8.5 kg
-25
Содержание Wallbox pro s
Страница 4: ...4 VI SENEC Wallbox pro s max 10mm max 10mm M 12 Nm V 210mm 105mm 260mm 16kg 1000 1100mm...
Страница 5: ...5 VII 9 17mm max 5 x 6mm M 8Nm M 4Nm Eska EADR25 Eska ESKV25 130mm 11 13mm 1N 230V 50Hz 3N 400V 50Hz...
Страница 6: ...6 VIII...
Страница 8: ...8 X 5 3 7 3mm max 2 x 0 5mm 100mm 30mm 6mm Chapter 1 8 3...
Страница 9: ...9 XI SENEC Wallbox pro s Chapter 2 2...
Страница 10: ...10 XII Chapter 2 2 2 SENEC Wallbox pro s t 5min S5 1 OFF ON S2 S6 S3 S4 S5 S5 S5...
Страница 11: ...11 t 5min 1 2 3 4 5 6 7 XIII XIV ON Chapter 2 2 2 SENEC Wallbox pro s SENEC Wallbox pro s...
Страница 12: ...12 XV Chapter 2 2 1 XVI 3 4 1 2 SENEC Wallbox pro s Chapter 1 7...
Страница 13: ...13 XVI SENEC Wallbox pro s 1 2 Chapter 1 8...
Страница 49: ...49 V 32A 1 2 3 4 5 5 1 1 1 4 2 2 2 3 3 3 16A 16A 6A 8A 8A 6A 10A 6A 6A 0A 6A 10A 10A 13A 13A 0A 6A 8A 6A 6A...
Страница 50: ...50 VI CAT6a max 500m 15mm 60mm 70mm 8mm VII...
Страница 51: ...51 VIII 3 5 2 1 4...
Страница 53: ...53 3 5 2 1 4 XI...
Страница 55: ...55 XIV S2 S6 S1 S3 S4 S5...