EN
L
IST OF
P
ARAMETERS
Symbol
Description of parameter
Range of values
Meas.unit
Min.
Max.
1
Energy unit price
0.01
325.00
[currency unit/kWh]
2
T
d
Daytime temperature
8.00
30.00
[°C]
3
T
n
Nighttime temperature
3.00
30.00
[°C]
4
Holiday time temperature
3.00
30.00
[°C]
5
Frost prevention temperature
0.00
10.00
[°C]
6
Individually set temperature in manual mode
3.00
30.00
[°C]
7
Correction of inner heat sensor
-5.00
5.00
[°C]
8
Correction of outter heat sensor
-5.00
5.00
[°C]
9
Timing of turn off in sweeper mode
5.00
60.00
[min]
10
T
h1
Hysteresis of burner in stage 1.
0.20
2.00
[°C]
11
T
h2
Delta-T of burner in stage 2.
0.10
15.00
[°C]
12
t
bonmin
Minimum operating time of burner
60.00
600.00
[sec]
13
t
s2delay
Delay of burner stage 2.
10.00
600.00
[sec]
14
t
vondelay
Delay time of fan start
0.00
10.00
[sec]
15
t
voffdelay
Delay time of fan shut-off
0.00
20.00
[min]
16
t
voffmin
Minimal idle time of fan
10.00
600.00
[sec]
17
Burner power in stage 1.
0.50
1000.00
[kW]
18
Total burner power
0.50
1000.00
[kW]
19
Correction of internal clock
-22.20
22.20
[sec/day]
Table 1: List of Parameters
T
ECHNICAL
D
ATA
Description of product:
EVO1
heating controller electronic unit
Mains supply:
230Vac 50Hz
Max. loadability of fan relay output:
16A(ohmic) 6A(inductive) 230Vac
Max. loadability of other relay outputs:
10A (ohmic) 230Vac
Power supply cable size:
3x1.5mm2
Fan cable size:
3x1.5mm2
Burner cable size:
5x1.5mm2
Sensors cable size:
UTP ~0.5mm2
Own power consumption of controller unit:
max. 4W
Fuse type(B1):
T250mA
(250V 5x20 glass tube slow fuses)
Maximal domain of operating temperature:
-20..+40°C
Box protection:
IP65
Table 2: Technical Data
15
Fig. 8.: Time Diagram