SEL-2241 Data Sheet

Schweitzer Engineering Laboratories, Inc.

6

Data Rate:

100 Mbps

Typical Fiber 

Attenuation:

–2 dB/km 

Single-Mode Option

Link Budget:

10 dB

Min. TX Power:

–15 dBm

Min. RX Sensitivity:

–25 dBm

Fiber Size:

9 µm

Approximate Range:

15 km

Data Rate:

100 Mbps

Typical Fiber 

Attenuation:

–0.4 dB/km 

Serial Ports

Ports:

4

Types:

EIA-232/EIA-485 (software selectable)

Data Rate:

300 to 115200 bps

Connector:

DB-9 Female

Time Synchronization:

IRIG-B

Power:

+5 Vdc power on Pin 1 

(500 mA maximum)

USB Ports

Device Ports:

1 Type B

Output Contact

Mechanical Durability:

10 M no-load operations

DC Output Ratings

Rated Operational 

Voltage:

250 Vdc

Rated Voltage Range:

19.2–275 Vdc

Rated Insulation Voltage: 300 Vdc

Make:

30 A @ 250 Vdc per IEEE C37.90

Continuous Carry:

6 A @ 70°C; 4 A @ 85°C

Thermal:

50 A for 1 s

Contact Protection:

360 Vdc, 40 J MOV

Operating Time (coil 

energization to contact 
closure, resistive load):

Pickup/Dropout time 

 8 ms typical

Breaking Capacity

(10,000 operations) per 

IEC 60255-0-20:1974:

24 Vdc

0.75 A

L/R = 40 ms

48 Vdc

0.50 A

L/R = 40 ms

125 Vdc

0.30 A

L/R = 40 ms

250 Vdc

0.20 A

L/R = 40 ms

Cyclic Capacity 

(2.5 cycles/second) per 
IEC 60255-0-20:1974:

24 Vdc

0.75 A

L/R = 40 ms

48 Vdc

0.50 A

L/R = 40 ms

125 Vdc

0.30 A

L/R = 40 ms

250 Vdc

0.20 A

L/R = 40 ms

AC Output Ratings

Rated Operational 

Voltage:

240 Vac

Rated Insulation Voltage: 300 Vac

Utilization Category:

AC-15 (control of electromagnetic 

loads > 72 VA)

Contact Rating 

Designation:

B300 (B = 5 A, 300 = rated insulation 

voltage)

Contact Protection:

270 Vac, 40 J

Continuous Carry:

3 A @ 120 Vac
1.5 A @ 240 Vac

Conventional Enclosed
Thermal Current (I

the

)

Rating:

5 A

Rated Frequency:

50/60 ± 5 Hz

Operating Time (coil 

energization to contact 
closure, resistive load):

Pickup/Dropout time < 8 ms typical

Electrical Durability 

Make VA Rating:

3600 VA, cosø = 0.3

Electrical Durability 

Break VA Rating:

360 VA, cosø = 0.3

Type Tests

Environmental Tests

Enclosure Protection:

IEC 60529:2001 + CRGD:2003
IP3X excluding the terminal blocks

Vibration Resistance:

IEC 60255-21-1:1988

Vibration Endurance, Severity: Class 2
Vibration Response, Severity: Class 1

Shock Resistance:

IEC 60255-21-2:1988

Bump Test, Severity: Class 1
Shock Withstand, Severity: Class 1
Shock Response, Severity: Class 1

Seismic:

IEC 60255-21-3:1993

Quake Response, Severity: Class 1

Cold:

IEC 60068-2-1:2007

–40°C, 16 hours

Dry Heat:

IEC 60068-2-2:2007

+85°C, 16 hours

Damp Heat, Cyclic:

IEC 60068-2-30:2005

25°C to 55°C, 6 cycles,
95% relative humidity

Dielectric Strength and Impulse Tests

Impulse:

IEC 60255-5:2000 

Severity Level: 0.5 J, 5 kV contact 
outputs; 0.5 J, 2 kV IRIG-B IN; 0.5 J, 
1.5 kV Ethernet ports

IEEE C37.90:2005 

Severity Level: 0.5 J, 5 kV contact 
outputs; 0.5 J, 2 kV IRIG-B IN; 0.5 J, 
1.5 kV Ethernet ports

Dielectric (HiPot):

IEC 60255-5:2000 

Severity Level: 2 kVac on contact output 
for 1 minute; 2 kVdc on IRIG-B IN and 
Ethernet ports for 1 minute

IEEE C37.90:2005

Severity Level: 2 kVac on contact output 
for 1 minute; 2 kVdc on IRIG-B IN and 
Ethernet ports for 1 minute

Insulation:

IEC 60255-5:2000 

Severity Level: 500 V for greater than 
1 minute

RFI and Interference Tests

EMC Immunity

Electrostatic Discharge 

Immunity:

IEEE C37.90.3:2001
IEC 60255-22-2:2008 
IEC 61000-4-2:2008 

Severity Level 4
8 kV contact discharge
15 kV air discharge

Radiated RF Immunity:

IEEE C37.90.2:2004 

Severity Level: 35 V/m

IEC 61000-4-3:2008

Severity Level: 10 V/m

IEC 60255-22-3:2007

Severity Level: 10 V/m

Содержание SEL-2241

Страница 1: ...2242 chassis backplane has ten slots labeled A through J Only Slot A supports the SEL 2241 RTAC module To install the RTAC tip the top of the module away from the chassis align the notch on the bottom...

Страница 2: ...eb interface through the USB cable See Section 7 Security and Account Management in the ACSELERATOR RTAC SEL 5033 Instruction Manual for RTAC web password setup The SEL 2241 has four nonisolated seria...

Страница 3: ...ection 1 Getting Started in the SEL 5033 Instruction Manual for instructions on how to back up and restore RTAC projects Step 2 De energize any power source connected to the power coupler s in the Axi...

Страница 4: ...ection 3 Factory Reset in the SEL 2240 Instruction Manual describes Table 3 shows the configurable jumper positions SEL 2241 Disassembly To disassemble the SEL 2241 RTAC perform the fol lowing steps S...

Страница 5: ...EtherNet IP Explicit Message Client Server DNP3 Serial DNP3 LAN WAN Modbus RTU Modbus TCP SEL Fast Messaging LG 8979 SES 92 IEEE C37 118 IEC 61850 MMS IEC 60870 5 101 104 FTP SFTP CDC Type II EtherNe...

Страница 6: ...Ithe Rating 5 A Rated Frequency 50 60 5 Hz Operating Time coil energization to contact closure resistive load Pickup Dropout time 8 ms typical Electrical Durability Make VA Rating 3600 VA cos 0 3 Elec...

Страница 7: ...Power Supply Immunity IEC 61000 4 11 2004 IEC 61000 4 29 2000 IEC 60255 11 2008 Magnetic Field Immunity IEC 61000 4 8 2009 Severity Level 1000 A m for 3 seconds 100 A m for 1 minute IEC 61000 4 10 200...

Страница 8: ...oducts including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice Schweitzer Engi...

Отзывы: