4.120
SEL-751A Relay
Instruction Manual
Date Code 20100129
Protection and Logic Functions
Front-Panel Settings (SET F Command)
=>>
SET F TERSE <Enter>
Front Panel
General Settings
DISPLY PTS ENABL (N,1-32) EDP := 5 ?
<Enter>
LOCAL BITS ENABL (N,1-32) ELB := N ?
2 <Enter>
LCD TIMEOUT (OFF,1-30 min) FP_TO := 15 ?
> <Enter>
•
•
•
Target LED Set
TRIP LATCH T_LED (Y,N) T01LEDL := Y ?
> <Enter>
Display Point Settings (maximum 60 characters):
(Boolean): Relay Word Bit Name, "Alias", "Set String", "Clear String"
(Analog) : Analog Quantity Name, "User Text and Formatting"
DISPLAY POINT DP01 (60 characters)
DP01 := IN101,"TRFR 1 HV BRKR:",CLOSED,OPEN
?
> <Enter>
Local Bits Labels:
LB_ NAME (14 characters; Enter NA to null)
NLB01 :=
?
SPERV SW <Enter>
CLEAR LB_ LABEL (7 characters; Enter NA to null)
CLB01 :=
?
OPEN <Enter>
SET LB_ LABEL (7 characters; Enter NA to null)
SLB01 :=
?
CLOSE <Enter>
PULSE LB_ LABEL (7 characters; Enter NA to null)
PLB01 :=
?
NA <Enter>
LB_ NAME (14 characters; Enter NA to null)
NLB02 :=
?
FAN START <Enter>
CLEAR LB_ LABEL (7 characters; Enter NA to null)
CLB02 :=
?
OFF <Enter>
SET LB_ LABEL (7 characters; Enter NA to null)
SLB02 :=
?
NA <Enter>
PULSE LB_ LABEL (7 characters; Enter NA to null)
PLB02 :=
?
START <Enter>
Save changes (Y,N)? Y
<Enter>
Settings Saved
=>>
Figure 4.74
Adding Two Local Bits
Target LED Settings
The SEL-751A offers the following two types of LEDs. See
and
for the programmable LED locations:
➤
Six Target LEDs
➤
Eight Pushbutton LEDs
Your can program all 14 LEDs using SEL
OGIC
control equations, the only
difference being that the Target LEDs also include a latch function.
Target LEDs
Settings T
n
_LEDL (
n
= 01 through 06) and T
n
_LED (
n
= 01 through 06)
control the six front-panel LEDs. With T
n
_LEDL set to Y, the LEDs latch
after assertion. To reset these latched LEDs, the corresponding LED equation
must be deasserted (logical 0) and one of the following takes place:
➤
Pressing
{TARGET RESET}
on the front panel.
➤
Issuing the serial port command
TAR R
.
➤
The assertion of the SEL
OGIC
equation RSTTRGT.
With T
n
LEDL settings set to N, the LEDs do not latch and directly follow the
state of the associated SEL
OGIC
control equation setting.
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...