U.5.43
Date Code 20090715
User’s Guide
SEL-421 Relay
Front-Panel Operations
Front-Panel Operator Control Pushbuttons
Figure 5.45
Factory Default Operator Control Pushbuttons
Press this operator control pushbutton to enable/disable user-programmed auxiliary control.
Program the corresponding LED to indicate the required state.
NOTE: This operator control does not perform any function with the factory settings.
PBn_LED
= 0
#AUX
AUX
SEL
OGIC
Factory
Setting
Operator
Control
Pushbutton LED
Description
Press this operator control pushbutton to trip Circuit Breaker 1. The corresponding BREAKER
OPEN LED illuminates, indicating that Circuit Breaker 1 is open.
PBn_LED
= NOT 52ACL1
and 52BCL1
and 52CCL1
#BREAKER OPEN
BREAKER
OPEN
Press this operator control pushbutton to close Circuit Breaker 1. The corresponding
BREAKER CLOSED LED illuminates indicating that Circuit Breaker 1 is closed. The MANUAL
CLOSE ENABLED function above enables and disables the CLOSE pushbutton.
PBn_LED
= 52ACL1 and
52BCL1 and
52CCL1
#BREAKER
CLOSED
BREAKER
CLOSED
Press this operator control pushbutton to enable/disable the automatic recloser. The
corresponding LED illuminates to indicate the RECLOSE ENABLED state.
PBn_LED
= PLT06
#RECLOSE
ENABLED
RECLOSE
ENABLED
Press this operator control pushbutton to enable/disable local front-panel circuit breaker
closing using the CLOSE pushbutton. The corresponding LED illuminates to indicate the
MANUAL CLOSE ENABLED state.
PBn_LED
= PLT05
#MANUAL
CLOSE ENABLED
MANUAL
CLOSE
ENABLED
Press this operator control pushbutton to enable/disable single-pole tripping. The
corresponding LED illuminates to indicate the SPT ENABLED state.
PBn_LED
= NOT E3PT
#SPT ENABLED
SPT
ENABLED
Press this operator control pushbutton to enable/disable communications-assisted tripping.
The corresponding LED illuminates to indicate the COMM SCHEME ENABLED state.
PBn_LED
= PLT02
#COMM SCHEME
ENABLED
COMM
SCHEME
ENABLED
Press this operator control pushbutton to enable/disable the relay test mode. The
corresponding LED illuminates to indicate the RELAY TEST MODE state.
PBn_LED
= PLT04
#RELAY
TEST MODE
RELAY
TEST
MODE
Press this operator control pushbutton for three seconds to switch the active setting group
between the main setting group (Setting Group 1) and the alternate setting group (Setting
Group 2). The corresponding LED illuminates to indicate the ALT SETTINGS state.
PBn_LED
= NOT SG1
#ALT SETTINGS
ALT
SETTINGS
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...